background image

Page 20 

                 

Installer’s Guide

Thermostat Heat Anticipator

Set the heat anticipator of the thermostat to equal the amperage 
draw of the gas valve

IMPORTANT:  

Upon completion of wiring, check all electrical con-

nections, including factory wiring within the unit.
Make sure all connections are tight. Replace and secure all electri-
cal box covers and access panels before leaving the unit or turning 
on the power to the unit.

Step 5—Unit Startup

 

Pre-Start Quick Checklist

  Is the unit properly located and level with the proper clearance?  

See Figure 4.

 Is the duct work correctly sized, run, taped, insulated, and 

weatherproofed with proper unit arrangement?  See Ductwork 
Installation section.

  Is the gas piping correctly sized, run, trapped, and purged of air?  

See Gas Piping section.

  Is the condensate line properly sized, run, trapped, and pitched?

  Is the filter of the correct size and number?  Is it clean and in 

place?

  Is the wiring properly sized and run according to the unit wiring 

diagram?

  Are all the wiring connections, including those in the unit, tight?

 

Has the unit been properly grounded and fused with the recom-
mended fuse size?  See Wiring Data.

  Is the thermostat level, correctly wired, well located, and set for 

the proper heat anticipation?

  Have the air conditioning systems been checked at the service 

ports for charge and leak tested if necessary?

  Does the condenser fan and indoor blower turn free without rub-

bing, and are they tight on the shafts?

  Has the indoor blower speed been determined and the proper 

speed been set?  See the Unit Wiring Diagram.

  Has all work been done in accordance with applicable local and 

national codes?

  Are all covers and access panels in place to prevent air loss and 

safety hazards?

Control Wiring (Class II)

Low voltage control wiring should not be run in conduit with power 
wiring unless Class 1 wire of proper voltage rating is used.  Route 
the thermostat cable or equivalent single leads of No. 18 AWG 
colored wire from the thermostat subbase terminals through the 
rubber grommet on the unit. See Figures 2 or 5 for the  control 
entry (24V Entry) location.  Make connections as shown on the 
unit wiring diagram.
Do not short thermostat wires since this will damage the control 
transformer.
Refer to Table 6 for recommended wire sizes and lengths for install-
ing the unit thermostat. The total resistance of these low voltage 
wires must not exceed one (1) ohm. Any resistance in excess of 1 
ohm may cause the control to malfunction because of the exces-
sive voltage drop.

Table 6. Thermostat Wire Size and Maximum Length

Contactor

Unit Ground Lug

Figure 20. Power Connections

e

z

i

S

e

r

i

h

W

t

g

n

e

L

m

u

m

i

x

a

M

8

5

1

7

6

5

1

2

1

4

0

1

0

2

Figure 21. Mounted Disconnect Location

Содержание 4YCY4042C

Страница 1: ...out the evaporator fan or coil access panels in place Reinstall the access panels after performing maintenance proceedures on the fan Operating the unit without the access panels properly installed ma...

Страница 2: ...per service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and approved POE compres sor oil IMPORTANT W...

Страница 3: ...work to Roof Frame 16 Attaching Horizontal Ductwork to Unit 16 Condensate Drain Piping 16 Gas Piping Installation 16 Pipe Delivery Schedule natural gas only 17 Gas Pressure Set up Precautions 17 Gas S...

Страница 4: ...Guide Step 2 Determine Unit Clearances Figure 1 4YCZ6036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from u...

Страница 5: ...Page 5 Installer s Guide Figure 2 4YCZ6036 2 of 3...

Страница 6: ...Page 6 Installer s Guide Figure 3 4YCZ6036 3 of 3...

Страница 7: ...Page 7 Installer s Guide Figure 4 4YCZ6048 through 4YCZ6060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Страница 8: ...Page 8 Installer s Guide Figure 5 4YCZ6048 through 4YCZ6060 2 of 3...

Страница 9: ...Page 9 Installer s Guide Figure 6 4YCZ6048 through 4YCZ6060 3 of 3...

Страница 10: ...to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricate...

Страница 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airfl...

Страница 12: ...abs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparing the unit for lifting check the unit dimension drawings for center of gravity for lifting safety Figur...

Страница 13: ...roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails are...

Страница 14: ...ible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars Base of unit rest on top of curb rails Dr...

Страница 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Ang...

Страница 16: ...ise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two...

Страница 17: ...making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local cod...

Страница 18: ...chonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the...

Страница 19: ...ns Models that require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1...

Страница 20: ...tioning systems been checked at the service ports for charge and leak tested if necessary Does the condenser fan and indoor blower turn free without rub bing and are they tight on the shafts Has the i...

Страница 21: ...Page 21 Installer s Guide Figure 22 4YCZ6 Field Wiring Diagram NOTE For economizer wiring instructions see the Installer s Guide that came with your economizer...

Страница 22: ...ating Cycle Theseunitsareequippedwithasolid stateignitioncontrolthatlights the burners each time the thermostat calls for heat The burners are extinguished during the OFF cycle The gas heating section...

Страница 23: ...nd postpurge The indoor blower motor will continue to operate at the current speed for 60 or 90 seconds after the flames are extinguished Sequence of Operation Safety Sequences This product is equippe...

Страница 24: ...stible materials gasoline or other flammable vapors or liquids near the unit WARNING Someoftheperiodicmaintenancefunctionsofthe4YCZ6unitcan beperformedbytheowner thisincludesreplacingthedisposable or...

Страница 25: ...Hood and Combustion Blower Cleaning Manifold Pressure Check and Adjust 1 Connect a manometer to the pressure tap at the outlet side of the unit s gas valve remove the Control Heat access panel Read th...

Страница 26: ...3 Flashes Pressure switch problem detected Fast Flash Rate Not used 4 Flashes High Limit switch protection device open Steady ON Normal No Call for Heat 5 Flashes Flame sensed and gas valve not energi...

Страница 27: ...Page 27 Installer s Guide...

Страница 28: ...ide Trane 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specification without n...

Отзывы: