18-GJ02D1-2 

 

5

Installer’s Guide

Airflow Performance  

2/4TGB3F30A1000A: Wet coil, No Heaters

EXTERNAL   

STATIC  

PRESSURE 

(in.w.g.)

AIRFLOW (CFM)

VERTICAL

HORIZONTAL

230 VOLTS 

208 VOLTS

230 VOLTS 

208 VOLTS

HIGH

MED

LOW

HIGH

MED

LOW

HIGH

MED

LOW

HIGH

MED

LOW

0

1114

988

841

976

835

699

1118

1014

858

992

856

721

0.1

1083

960

817

941

818

682

1080

979

836

969

839

702

0.2

1046

935

799

914

801

665

1036

947

815

939

820

686

0.3

1004

908

781

887

781

647

990

913

792

905

798

669

0.4

958

875

757

856

756

625

942

874

764

867

770

648

0.5

908

834

723

818

725

597

893

827

729

824

734

619

0.6

851

782

679

770

684

562

838

770

685

772

688

581

0.7

783

719

624

708

632

519

772

705

630

709

631

532

0.8

699

645

560

633

565

466

685

630

563

629

562

471

0.9

594

560

491

545

483

404

565

548

485

526

479

398

NOTES:

With filter, no horizontal drip tray  - Small apex baffle

As shipped, with filter

Airflow Performance   

2/4TGB3F36A1000A: Wet coil, No Heaters

EXTERNAL   

STATIC  

PRESSURE  

(in.w.g.)

AIRFLOW (CFM)

VERTICAL

HORIZONTAL

230 VOLTS 

208 VOLTS

230 VOLTS 

208 VOLTS

HIGH

MED

LOW

HIGH

MED

LOW

HIGH

MED

LOW

HIGH

MED

LOW

0

1305

1191

1102

1239

1062

957

1262

1187

1112

1211

1080

967

0.1

1259

1154

1076

1200

1039

947

1211

1146

1080

1164

1051

948

0.2

1209

1112

1041

1154

1012

924

1156

1082

1031

1114

1007

930

0.3

1156

1066

1001

1105

980

895

1099

1012

975

1062

955

902

0.4

1101

1018

958

1054

941

863

1044

946

917

1009

901

858

0.5

1043

968

910

1000

896

826

986

888

860

952

845

797

0.6

981

911

857

939

841

781

922

832

800

889

785

722

0.7

911

843

793

866

776

721

843

768

731

813

715

641

0.8

832

757

713

773

697

636

738

676

641

717

627

568

0.9

739

641

610

649

603

511

593

531

517

592

510

520

NOTES:

With filter, no horizontal drip tray - Small apex baffle

As shipped, with filter

Airflow Performance 

2/4TGB3F42A1000A: Wet coil, No Heaters

EXTERNAL  

STATIC

PRESSURE

(in.w.g.)

AIRFLOW (CFM)

VERTICAL

HORIZONTAL

230 VOLTS 

208 VOLTS

230 VOLTS 

208 VOLTS

HIGH

M-HI

LOW

HIGH

M-HI

LOW

HIGH

M-HI

LOW

HIGH

M-HI

LOW

0

1925

1823

1432

1833

1691

1212

1870

1788

1424

1786

1674

1662

0.1

1850

1753

1399

1758

1636

1192

1791

1724

1397

1728

1612

1621

0.2

1765

1676

1363

1686

1563

1168

1717

1648

1358

1657

1545

1558

0.3

1673

1597

1317

1611

1489

1136

1641

1569

1309

1580

1476

1491

0.4

1579

1518

1255

1530

1421

1091

1559

1490

1251

1500

1404

1422

0.5

1484

1440

1175

1439

1358

1031

1466

1411

1184

1416

1328

1350

0.6

1388

1358

1078

1340

1286

956

1363

1326

1105

1326

1244

1262

0.7

1292

1266

966

1233

1182

868

1249

1225

1014

1223

1146

1135

0.8

1192

1154

846

1123

1013

769

1127

1090

906

1096

1027

940

0.9

1084

1008

726

1015

734

663

1003

900

778

933

878

636

NOTES:

With filter, no horizontal drip tray - Small apex baffle

As shipped, with filter

Airflo

w P

erf

or

mance 

Tab

les contin

ued on bac

k page

.

Содержание 2/4TGB3F018A

Страница 1: ... Regulations Chapter XX Part 3280 or the equivalent SUIT ABLE FOR MOBILE HOME USE For proper installation the following items must be considered 1 If adequate power is available and correct according to nameplate specifica tions 2 Pursuant to Florida Building Code 13 610 2 A 2 1 this unit meets the criteria for a factory sealed air handler 3 Insulate and seal all ducts particularly if unit is loca...

Страница 2: ...g as the unit is supported from both ends as well as the middle to prevent sagging and service access is not obstructed e If the unit is not suspended it must be isolated carefully to prevent sound trans mission Vibration isolators purchased locally must be placed under the unit C DUCT CONNECTIONS The supply and return air ducts should be connected to the unit with flame retardant duct connectors ...

Страница 3: ...he outside of the air handler and the conduit terminated to it The electrical connections are made using the two power leads and ground wire connections which are located near the discharge of the blower NOTE If air handler is used with or without a heater the 7 8 electrical entry hole as well as any other cabinet penetrations must be sealed air tight WARNING ELECTRICAL SHOCK HAZARD LOCK OUT UNIT ...

Страница 4: ... 419 364 198 468 418 277 401 357 191 0 9 385 347 164 322 263 78 378 335 172 316 267 75 NOTES With filter no horizontal drip tray Small apex baffle As shipped with filter Airflow Performance 2 4TGB3F25A1000A Wet coil No Heaters EXTERNAL STATIC PRESSURE in w g AIRFLOW CFM VERTICAL HORIZONTAL 230 VOLTS 208 VOLTS 230 VOLTS 208 VOLTS HIGH MED LOW HIGH MED LOW HIGH MED LOW HIGH MED LOW 0 1035 965 773 92...

Страница 5: ... 1007 930 0 3 1156 1066 1001 1105 980 895 1099 1012 975 1062 955 902 0 4 1101 1018 958 1054 941 863 1044 946 917 1009 901 858 0 5 1043 968 910 1000 896 826 986 888 860 952 845 797 0 6 981 911 857 939 841 781 922 832 800 889 785 722 0 7 911 843 793 866 776 721 843 768 731 813 715 641 0 8 832 757 713 773 697 636 738 676 641 717 627 568 0 9 739 641 610 649 603 511 593 531 517 592 510 520 NOTES With f...

Страница 6: ...6 18 GJ02D1 2 Installer s Guide OUTLINE DRAWING FOR 2 4TGB3F18 36A D810094REV05 ...

Страница 7: ...18 GJ02D1 2 7 Installer s Guide D810126REV04 OUTLINE DRAWING FOR 2 4TGB3F42 48A ...

Страница 8: ...limitations and recommendations to determine if the heater requires a SPECIAL CIRCUIT 1 Be sure the disconnect switch is OFF and safety label if any is attached 2 Check on field wiring for tight connections and grounding according to codes 3 Check circuit protection for proper size per nameplate specifications 4 Check control box panel in place and secured NOTE OPERATION OF HEATERS MUST BE CHECKED...

Отзывы: