background image

 

18-GJ02D1-2

Installer’s Guide

  f.  It is always recommended that an auxiliary drain pan be installed under a hori-

zontal air handler (See Condensate Drain Piping) to prevent possible damage to 

ceilings.

  g.  Isolate the auxiliary drain pan from the unit or from the structure.
  h.  Connect the auxiliary drain line to a separate drain line (no trap is needed in this 

line) and terminate according to local codes. 

  i.  If a return duct is connected to the Air Handler, it must be the same dimensions 

as the return opening shown in the outline drawings. 

Remove
and 
Discard

Replace
with 
Narrow
Baffle

Figure 1. For Maximum Efficiency on Upflow 

2/4TGB3F042A & 2/4TGB3F048A Only

handler must be made to allow access for refrigerant lines, or attach refrigerant 

lines to air handler when installing. 

  11.  Make sure there are provisions for installing condensate drain lines.
  12.  Route refrigerant & condensate drain lines away from air handler so they do not 

interfere with access panels and filters.

  13.  When external accessories are used, the additional height and width require-

ments must be considered in the overall space needed.

  14.  These units are not approved for outdoor installation.
  15.  These units are approved for draw-through application only.

  B.  UNIT INSTALLATION
 UPFLOW

  a.  For maximum efficiency, the horizontal drip tray should be removed. Tray 

removal requires that the coil be removed by sliding the coil out on the coil 

channel supports. The tray is detached by removing the two screws at the drain 

pan and the two screws holding the two brackets at the top of the coil.

  b.  Openings where field wiring enters the cabinet must be completely sealed. The 

Refrigerant lines must be sealed and Electrical inlets need to be sealed both 

the low and the high voltage. Location of power entry is shown on the Outline 

Drawing.  

  c. 

2/4TGB3F042A & 2/4TGB3F 48A Only: 

Remove the factory installed baffle 

assembly from the apex of the coil by removing the 5/16" hex head screws. 

 

  Replace this baffle with the factory supplied narrow coil baffle using the screws 

removed previously (See Figure 1). 

  d.  Position unit on Pedestal or other suitable foundation. If Pedestal is not used, 

a frame strong enough to support the total weight must be provided. Provide a 

minimum height of 14 inches for proper unrestricted airflow. 

  e.  If a return air duct is connected to the air handler, it must be the same dimen-

sions as shown in the outline drawing.

  f.  Pedestal and unit should be isolated from the foundation using a suitable isolat-

ing material.

HORIZONTAL LEFT

   a.  For maximum efficiency and Customer ease of filter maintenance, it is recom-

mended that a properly sized remote filter and grille be installed for horizontal 

applications. Airflow should not exceed the face velocity of the filter being used. 

The factory installed filter should then be removed from the unit.

  b.  The unit is shipped from the factory in the horizontal left airflow position.
  c.  Openings where field wiring enters the cabinet must be completely sealed . The 

Refrigerant lines must be sealed and Electrical inlets need to be sealed both 

the low and the high voltage.Location of power entry is shown on the Outline 

Drawing.  

  d.  The unit may be suspended as long as the unit is supported from both ends as 

well as the middle to prevent sagging and service access is not obstructed.

  e.  If the unit is not suspended it must be isolated carefully to prevent sound trans-

mission. Vibration isolators (purchased locally) must be placed under the unit.

  C.  DUCT CONNECTIONS  

The supply and return air ducts should be connected to the unit with flame retardant 

duct connectors.
Convertible duct flanges can be field fabricated to make a “flush fit” for ¾” or 1-1/2” 

ductboard applications.  See the Outline drawing for sizes of the discharge opening 

and flange dimensions. After ductwork is secured, seal the ductwork per local and 

national codes to prevent air loss/infiltration.

D. Refrigerant Piping

IMPORTANT: Refrigerant piping must be routed to maintain service access to 

blower compartment and provide easy removal of filter access panel and filter.

  1.  Refrigerant connections are made outside the cabinet.

NOTE: TXV bulb MUST be protected (wrap a wet rag around the suction line 

between the TXV bulb and the braze joint) or removed, while brazing the tubing. 

Overheating of the sensing bulb will affect the functional characteristics and 

performance of the air handler.

  2.  If changing the Thermostatic valve (TEV/TXV), be sure to use a wrench and 

backup wrench to tighten the mechanical fittings 1/6 turn past finger tight upon 

installation.

  3.  Installation of refrigerant lines is covered in the installation instructions pack-

aged with the outdoor unit. Evacuation, leak testing and brazing procedures are 

included in those instructions. Read those instructions before starting installa-

tion of refrigerant lines.

NOTE: TXV Equipped is Non-Bleed, and may require a start kit on the outdoor 

unit.

NOTE: Refrigerant line openings must be sealed along with field wiring.

E.  BRAZING TO EVAPORATOR SECTION

IMPORTANT: Do not unseal refrigerant tubing until ready to cut and fit refriger-

ant lines.

  1.  Remove the sealing caps from indoor coil field connections.
  2.  Field supplied tubing should be cut squared-off, ensuring the tube is still round 

and free of burrs at the connecting end. Clean the tubing to prevent contami-

nants from entering the system.

  3.  Run refrigerant tubing into the stub sockets of indoor unit coil.  Refrigerant line 

openings must be completely sealed.

  4.  Braze and evacuate according to indoor and outdoor installation instructions.

NOTE: Painted areas of unit must be shielded during brazing.

F.  CONDENSATE DRAIN PIPING

NOTE: Make certain that the unit has been installed in a level position to ensure 

proper draining.

The indoor blower is downstream of the evaporator coil which creates a negative 

pressure at the condensate drain connections during operation. The condensate 

drain connections in front of the indoor coil are 3/4" NPT. The lower connection is the 

primary drain. See Figure 2.
Two secondary drain connections are provided for the different orientations (See Fig-

ure 2). The lower of the two should be connected as a backup to prevent condensate 

overflow by a blocked primary drain. The weep hole in center of drain coupling area 

should be sealed with caulk or RTV.
For proper drainage of condensate, the following steps should be followed:
  1.  The primary drain line must be trapped with a minimum of 2" water seal as 

shown in Figure 3.

Figure 2. Condensate Drain Locations

3/4" NPT  

Primary drain  

connection

3/4" NPT Secondary

drain connection

Seal weep hole

Содержание 2/4TGB3F018A

Страница 1: ... Regulations Chapter XX Part 3280 or the equivalent SUIT ABLE FOR MOBILE HOME USE For proper installation the following items must be considered 1 If adequate power is available and correct according to nameplate specifica tions 2 Pursuant to Florida Building Code 13 610 2 A 2 1 this unit meets the criteria for a factory sealed air handler 3 Insulate and seal all ducts particularly if unit is loca...

Страница 2: ...g as the unit is supported from both ends as well as the middle to prevent sagging and service access is not obstructed e If the unit is not suspended it must be isolated carefully to prevent sound trans mission Vibration isolators purchased locally must be placed under the unit C DUCT CONNECTIONS The supply and return air ducts should be connected to the unit with flame retardant duct connectors ...

Страница 3: ...he outside of the air handler and the conduit terminated to it The electrical connections are made using the two power leads and ground wire connections which are located near the discharge of the blower NOTE If air handler is used with or without a heater the 7 8 electrical entry hole as well as any other cabinet penetrations must be sealed air tight WARNING ELECTRICAL SHOCK HAZARD LOCK OUT UNIT ...

Страница 4: ... 419 364 198 468 418 277 401 357 191 0 9 385 347 164 322 263 78 378 335 172 316 267 75 NOTES With filter no horizontal drip tray Small apex baffle As shipped with filter Airflow Performance 2 4TGB3F25A1000A Wet coil No Heaters EXTERNAL STATIC PRESSURE in w g AIRFLOW CFM VERTICAL HORIZONTAL 230 VOLTS 208 VOLTS 230 VOLTS 208 VOLTS HIGH MED LOW HIGH MED LOW HIGH MED LOW HIGH MED LOW 0 1035 965 773 92...

Страница 5: ... 1007 930 0 3 1156 1066 1001 1105 980 895 1099 1012 975 1062 955 902 0 4 1101 1018 958 1054 941 863 1044 946 917 1009 901 858 0 5 1043 968 910 1000 896 826 986 888 860 952 845 797 0 6 981 911 857 939 841 781 922 832 800 889 785 722 0 7 911 843 793 866 776 721 843 768 731 813 715 641 0 8 832 757 713 773 697 636 738 676 641 717 627 568 0 9 739 641 610 649 603 511 593 531 517 592 510 520 NOTES With f...

Страница 6: ...6 18 GJ02D1 2 Installer s Guide OUTLINE DRAWING FOR 2 4TGB3F18 36A D810094REV05 ...

Страница 7: ...18 GJ02D1 2 7 Installer s Guide D810126REV04 OUTLINE DRAWING FOR 2 4TGB3F42 48A ...

Страница 8: ...limitations and recommendations to determine if the heater requires a SPECIAL CIRCUIT 1 Be sure the disconnect switch is OFF and safety label if any is attached 2 Check on field wiring for tight connections and grounding according to codes 3 Check circuit protection for proper size per nameplate specifications 4 Check control box panel in place and secured NOTE OPERATION OF HEATERS MUST BE CHECKED...

Отзывы: