Causes of Faults and Remedies
Printed in the Federal Republic of Germany
©
TR-Electronic GmbH 2007, All Rights Reserved
14.12.2007
TR - ELE - BA - GB - 0008 - 06
Page 33 of 37
6.2.12 Save parameters
Via this parameter all programmed parameters are saved permanently. The
parameters are also available after switch on the laser again.
Parameter-No.
B12 B9
Parameter value in
D0 - D24
Value range
Default
1 1 1 1
0
0 -
7 Causes of Faults and Remedies
The fault causes are defined according to the malfunction code (see page 27). For the
resetting of the malfunction code, at first the error must be eliminated. After this the
device control command "Enable Operation" must be sent to the laser. If the switching
input was adjusted via the TRWinProg-software for error resetting, the error can be
acknowledged also about the external switching input.
Malfunction
Code
Cause
Remedy
0001
Invalid parameters
from the host
Invalid parameter
data, a parameter
range error is
available.
Check all programmed parameters after valid ranges of
values (see "Parameter overview", page 26 and
"Parameter description", starting from page 30).
0011
Memory error
Hardware error
If the error occurs at repeated service type, the device
must be replaced.
1001
Intensity warning
The device deter-
mined an intensity of
< 12%.
This message is only a warning and means that the
measuring system optics, or the reflecting foil is to be
cleaned. However, the device operates error-freely
furthermore.
1010
Laser diode
switched off
The bit is set, if the
laser diode was
switched off over the
bus, or the switching
input.
Serves only for information purposes.
1100
Intensity error
The device checks
the intensity of the
received laser signal
continuously, it was
detected a below-
minimum intensity.
1.
Clean measuring system optics
2.
Clean reflecting foil
3.
Rule out an interruption of the laser beam
If the possibility of soiling or interruption of the laser signal
can be ruled out, the device must be replaced.
1101
Speed-check
The adjusted speed
level was exceeded.
Serves only for information purposes, whether the adjusted
speed level was exceeded. (Function see chapter 5.2,
page 20 and chapter 6.2.7, page 31).
1110
Device temperature
The temperature has
exceeded or fallen
short of the range of
0 - 50°C in the
housing of the device.
Appropriate measures must be taken to prevent the device
from overheating or undercooling.
1111
Plausibility warning
The plausibility of the
measured value
couldn't be guaran-
teed any more.
This message is a warning and means that possibly
corresponding measures must be taken, so that no system
components will be damaged.