Configuration / Parameter setting via the Interbus-S master
©
TR-Electronic GmbH 2007, All Rights Reserved
Printed in the Federal Republic of Germany
Page 32 of 37
TR - ELE - BA - GB - 0008 - 06
14.12.2007
6.2.8 Error value
Determination of the error value which is output instead of the actual value at a beam
interruption.
Parameter-No.
B12 B9
Parameter value in
D0 - D24
Value range
Default
1 0 1 0
0 = NULL
1 = 0xFF
2 = Last valid position value
0 - 2
0
6.2.9 Function external input
Determines, whether the switching input is to be used as
-
Preset input, - Switch-off Laser-Diode (LD) or Failure reset - input
With connection of the switching input as Preset-input the laser is adjusted on the
predefined position value (see also "Preset preselection", page 31). With connection
the switching input as LD-input the laser diode is switched off for the extension of the
life time. If in the PC-program "TRWinProg" in the basic parameters the switching-off
of the laser diode is carried out automatically, the LD-switching input does not have a
function.
Parameter-No.
B12 B9
Parameter value in
D0 - D24
Value range
Default
1 1 0 0
0 = disabled
1 = Preset
2 = Switch off laser diode
3 = Failure quit
0 - 3
0
6.2.10 Clear Preset
Via this parameter, the zero-point correction calculated under the parameter
"Preset preselection, 0100" is deleted. The correction arises from the difference of the
desired preset value to the physical laser position. That means, after deletion of the
zero-point correction the laser outputs his "real" physical position.
Parameter-No.
B12 B9
Parameter value in
D0 - D24
Value range
Default
1 1 0 1
0 = no clearing
1 = clear Preset
0 - 1
0
6.2.11 Function external output
Specifies the function of the error output (external switching output). Definition of the
error see "Malfunction code", page 27 and "Causes of Faults and Remedies", page 33.
Options:
Parameter-No.
B12 B9
Parameter value in
D0 - D24
Value range
Default
1 1 1 0
0 = disabled
1 = Temperature
2 = Intensity
3 = Hardware-Fail
4 = every fail
5 = Speed-check
6 = Plausibility measured value
0 – 6
0