15
Compressor ON C. D Period
Outdoor fan motor OFF
30s 30 s 30 s
Indoor fan motor ON
Set fan speed OFF
0 3 6 9 12 Minutes
Begin Detecting the temp.
Decide the working period
2. Dehumidifying function:
As following chart, dehumidifying function begin a circle every 8 minutes, after continuing 7 circles, go back to “3.
Begin to operation”, and begin a new circle.
Compressor ON A Period B Period
Outdoor fan motor OFF
30 s
30 s
Low flow ON
Indoor fan motor OFF
0 4 8 0 4 8 minutes
Compressor ON D Period C Period
Outdoor fan motor OFF
30 s
30 s
Low flow ON 30 s
Indoor fan motor OFF
0 4 8 0 4 8 minutes
Continued working function in Dehumidifying Mode:
Continued Dehumidifying mode function (CONT) is similar as the Continued Cooling mode (when indoor fan motor is set as
AUTO or HI, the unit will change from Middle flow mode into Low flow mode after 12 minutes).
三
三
三
三
. Fan mode