Vent pipe:
Install vent pipe through the wall thimble and attach to fl ue outlet collar on top of the fi replace.
Secure all joints with screws and seal with approved "High Temp." self-adhesive aluminum
tape provided.
Adjust the fi replace position so that the vent pipe does not protrude beyond the outer
wall. The vent connector on the termination will accomodate walls up to 12" thick.
Wall vent terminal:
1) Engage the terminal with the vent pipe and slide terminal into place. Ensure that both
inner and outer pipes are fully engaged and then attach the terminal to the outside wall.
The vent terminal must not be recessed into the exterior wall or siding
.
2) Caulk in place to prevent any moisture entering the building.
NOTE: MINIMUM CLEARANCES TO THE VENT TERMINAL MUST BE MAINTAINED
(see Fig. #40 & 41).
Fig. #33
HORIZONTAL
TERMINAL
TCVT.9360
14 1/2" FRAMED
OPENING
WALL SHIELD THIMBLE
TCVT.THIMA
ELBOW
TCVT.811XLB90
24"
VENT PIPE
TCVT.811X24
12" VENT PIPE
TCVT.811X12
* Minimum height from the fl oor to center of the
opening with a maximum horizontal run of 18"
from the center of the fl ue outlet to the outside
face of the outer wall. The height will need to be
increased if a longer horizontal pipe is required.
*
68 1/2"
20
TC36.CODE 102513-40