Response time limit
Designates a time used to limit the response time from the remote station in 0.1 second
units.
F
E
0
A+7
(c) Status (See 7.3 (5) for details on bits C, D, E, and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
0
0
0
0
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
(d) Important items
•
The command number (0000H) is the same as the "Data Write".
•
A transfer size error (TermSTS = 09H) occurs if the transferred register data length exceeds
the range 1 to 128 words (or 1 to 83 words for the T and C registers).
•
A register designation error (TermSTS = 01H) occurs if a value other than a stipulated value
is designated for the register type codes (Register type (self/target-station)).
•
A register designation error (TermSTS = 01H) occurs if 0007H (the T register) is designated
for the local station register type code and a register other than T register is designated for
the remote station register type code. This also holds for the C register.
•
A boundary error (TermSTS = 0AH) occurs if a range spanning both the base T registers
(0 to 511) and the expansion T registers (512 to 999) is designated for the T register.
•
For data storage registers, a boundary error occurs if the designated area (leading a
register range) does not exist in either the local or remote stations.
Local station : TermSTS = 0AH ; Remote station : TermSTS = 8AH
•
A response time-out error (TermSTS = 02H) occurs if the response time from the remote
station exceeds the time designated by the response time limit.
0: Use the user-specified value (0.1 to 3276.7 seconds)
1: Use the default value of 30 seconds.