44
6
F
3
B
0
3
5
6
(5) Sample program
This program transmit the data from TOSLINE-S20LP's scan data memory to T2N/T3H's D
register. If the following program is executing, the data of the scan memory from 0000 to
0009 are transmitted to the data register from D0200 to D0209 (D register).
Source designation
Transfer size
Destination designation
RW003
H01
H10
RW005
00010
RW020
H00
H04
RW004
00000
RW021
00200
Channel 1 S20LP
10 Words transfer
D0200 (CPU register)
Scan memory address
•
Operation
When X0000 is ON, 10 words data starting with scan memory address 0 is transferred to
D0200 and after.
TOSLINE-S20LP
T2N/T3H’s CPU
scan data memory source
register designation
00001
D0200
00001
00100
D0201
00100
12345
D0202
12345
Transmit
03344
D0207
03344
11565
D0208
11565
00045
D0209
00045
[00272 MOV RW003]
[00000 MOV RW004]
[00010 MOV RW005]
X0000
[00004 MOV RW020]
[00200 MOV RW021]
[RW003 XFER RW005 RW020]
H0110
00010
H0004