3.
System Configuration Unit and Module
94
Analog Output Module SAO06
SAO06 module specifications
Item
Specification
Model name
SAO06
Number of output points
8 points
Output isolation unit
8 points are isolated together (output (-) side common).
Output signal level
4-20 mAdc
Load resistance range
0 to 600
Through-rate
10 ms or less (0 to 90%, resistance load)
D/A conversion data
+800 to +4000 counts
CMRR
100 dB or more (100 Vac-50/60 Hz)
Standard output accuracy
Within
0.125% of full scale
Load fluctuation
Within
0.05% (250
standard)
Temperature drift
Within
0.01%/
C
Supply voltage drift
0.1%/full-scale (system power supply variation
10%)
Output ripple
Within
0.5% of full scale
Diagnosis of trouble
Output current lead-back*, transmission, CPU, memory
Dualization
Possible (Two units are mounted on the UTBA6 terminal block
units.)
Dualized switching condition
When a major alarm has occurred to the online module
Output bump at dualized
switching
Stabilized within 1ms (when the data output is constant)
Address settings
Set from 1 to E (decimal 1 to 14) by front panel address setting
switch. When dualized, the pair is set for the same address.
Output specification in
emergency
HOLD mode (output hold) or RESET mode (output OFF) can be
selected.
Insulation resistance
100 M
or more (measured with 500 Vdc megger, between
outputs and internal circuits)
Ability of insulation to withstand
voltage
500 Vac for 1 minute (between inputs and internal circuits)
Current consumption
24 Vdc-200 mA or less (system power supply)
Internal heat generation
4.8 W or less
Compatible terminal block unit
UTBA1 (for single configuration), UTBA6 (for dualized configuration)
Compatible options
-
Compatible communication
module
SBIF2
I/O bus transmission speed
375 kbps
External dimensions
40 W
90 H
95 D mm (excluding protrusions)
Weight
200 g or less
* Read-back error occurs during output disconnecting.
Содержание TOSDIC-CIE DS
Страница 1: ...Toshiba Integrated Control System Intelligent PI O Instruction Manual 6F8C0779 ...
Страница 10: ...Introduction viii ...
Страница 14: ...Contents xii ...
Страница 20: ...1 System Configuration 6 ...
Страница 40: ...2 Installation and Wiring 26 ...
Страница 53: ...3 System Configuration Unit and Module 39 UTBA1 front panel ...
Страница 56: ...3 System Configuration Unit and Module 42 UTBA2 front panel ...
Страница 59: ...3 System Configuration Unit and Module 45 UTBA3 front panel ...
Страница 68: ...3 System Configuration Unit and Module 54 UTBD1 front panel ...
Страница 71: ...3 System Configuration Unit and Module 57 UTRC1 front panel ...
Страница 142: ......
Страница 151: ...Apendix 2 External Dimentions 137 Terminal Block Unit Appended Figure 2 2 Terminal block unit ...
Страница 156: ......
Страница 158: ...TOSHIBA CORPRATION 72 34 Horikawacho Saiwai ku Kawasaki shi Kanagawa 212 8585 JAPAN ...