3.
System Configuration Unit and Module
58
UTRC1 - Table of signal correspondences between I/O relay terminals
SDI01
SDO01
Relay unit terminal
Corresponding connectors
DI1
DO1
0-C0
Upper level PI/O module CN3
DI2
DO2
1-C1
Lower level PI/O module CN5
DI3
DO3
2-C2
DI4
DO4
3-C3
DI5
DO5
4-C4
DI6
DO6
5-C5
DI7
DO7
6-C6
DI8
DO8
7-C7
DI9
DO9
8-C8
DI10
DO10
9-C9
DI11
DO11
10-C10
DI12
DO12
11-C11
DI13
DO13
12-C12
DI14
DO14
13-C13
DI15
DO15
14-C14
DI16
DO16
15-C15
DI17
DO17
0-C0
Upper level PI/O module CN4
DI18
DO18
1-C1
Lower level PI/O module CN6
DI19
DO19
2-C2
DI20
DO20
3-C3
DI21
DO21
4-C4
DI22
DO22
5-C5
DI23
DO23
6-C6
DI24
DO24
7-C7
DI25
DO25
8-C8
DI26
DO26
9-C9
DI27
DO27
10-C10
DI28
DO28
11-C11
DI29
DO29
12-C12
DI30
DO30
13-C13
DI31
DO31
14-C14
DI32
DO32
15-C15
(Note) The signal correspondences given here are for the case in which an Omron
G79-**C cable with connector is used.
NOTICE:
One mounted SDI01 or SDO01 module controls 2 relay units (16 points). Input and
output relays should not be mixed among these 32 points.
Doing so can cause misoperation.
24 Vdc and 0V (external power supply) are connected on the relay unit side. The
external power supply is connected in common in 32-point (2 relay unit) units. Always
connect the same power supply to the 2 relay units.
Failure to do so can cause misoperation.
Always cover the unused connectors (CN3 to CN6) with connector covers.
Otherwise the insulation may deteriorate and the connector pins may corrode.
Содержание TOSDIC-CIE DS
Страница 1: ...Toshiba Integrated Control System Intelligent PI O Instruction Manual 6F8C0779 ...
Страница 10: ...Introduction viii ...
Страница 14: ...Contents xii ...
Страница 20: ...1 System Configuration 6 ...
Страница 40: ...2 Installation and Wiring 26 ...
Страница 53: ...3 System Configuration Unit and Module 39 UTBA1 front panel ...
Страница 56: ...3 System Configuration Unit and Module 42 UTBA2 front panel ...
Страница 59: ...3 System Configuration Unit and Module 45 UTBA3 front panel ...
Страница 68: ...3 System Configuration Unit and Module 54 UTBD1 front panel ...
Страница 71: ...3 System Configuration Unit and Module 57 UTRC1 front panel ...
Страница 142: ......
Страница 151: ...Apendix 2 External Dimentions 137 Terminal Block Unit Appended Figure 2 2 Terminal block unit ...
Страница 156: ......
Страница 158: ...TOSHIBA CORPRATION 72 34 Horikawacho Saiwai ku Kawasaki shi Kanagawa 212 8585 JAPAN ...