3.
System Configuration Unit and Module
43
UTBA2 terminal block (TB1, TB2) signal table
TB1
PI/O module
TB2
SAI02
SAI03
SRT01
SAO02
FG (0) FG
FG
FG
FG
1
AI1 (+)
AI1 (+)
RTD1 (A)
AO1 (+)
2
AI1 (-)
AI1 (-)
RTD1 (B)
AO1 (-)
3
DP1
RTD1 (b)
4
Shield 1
Shield 1
Shield 1
Shield 1
5
AI2 (+)
AI2 (+)
RTD2 (A)
AO2 (+)
6
AI2 (-)
AI2 (-)
RTD2 (B)
AO2 (-)
7
DP2
RTD2 (b)
8
Shield 2
Shield 2
Shield 2
Shield 2
9
AI3 (+)
AI3 (+)
RTD3 (A)
AO3 (+)
10
AI3 (-)
AI3 (-)
RTD3 (B)
AO3 (-)
11
DP3
RTD3 (b)
12
Shield 3
Shield 3
Shield 3
Shield 3
13
AI4 (+)
AI4 (+)
RTD4 (A)
AO4 (+)
14
AI4 (-)
AI4 (-)
RTD4 (B)
AO4 (-)
15
DP4
RTD4 (b)
16
Shield 4
Shield 4
Shield 4
Shield 4
17
18
19
20
NOTICE:
Before mounting a PI/O module, check to make sure that the connected signal matches
the mounted PI/O module rating.
If a PI/O module is mounted and an erroneous signal is connected, the PI/O module or external
sensor may got damage.
Each terminal block shield (4 terminals) is connected internally to each FG terminal.
The shield and PI/O are grounded by grounding the FG terminals. Always ground them.
Otherwise parts will be damaged or system will be malfunction.
Do not connect an external signal line or power supply line to an open terminal.
Doing so may cause parts to be damaged or malfunction.
Содержание TOSDIC-CIE DS
Страница 1: ...Toshiba Integrated Control System Intelligent PI O Instruction Manual 6F8C0779 ...
Страница 10: ...Introduction viii ...
Страница 14: ...Contents xii ...
Страница 20: ...1 System Configuration 6 ...
Страница 40: ...2 Installation and Wiring 26 ...
Страница 53: ...3 System Configuration Unit and Module 39 UTBA1 front panel ...
Страница 56: ...3 System Configuration Unit and Module 42 UTBA2 front panel ...
Страница 59: ...3 System Configuration Unit and Module 45 UTBA3 front panel ...
Страница 68: ...3 System Configuration Unit and Module 54 UTBD1 front panel ...
Страница 71: ...3 System Configuration Unit and Module 57 UTRC1 front panel ...
Страница 142: ......
Страница 151: ...Apendix 2 External Dimentions 137 Terminal Block Unit Appended Figure 2 2 Terminal block unit ...
Страница 156: ......
Страница 158: ...TOSHIBA CORPRATION 72 34 Horikawacho Saiwai ku Kawasaki shi Kanagawa 212 8585 JAPAN ...