TMC7 SERIES
TMC7 Series
Page 12
710-02887-00A
4.4 Control
Circuits
Control Voltage
2 Wire Control
3 Wire Control
24 VAC/VDC (C2 models)
24 VAC/VDC
(+)
(-)
A3
A1
A2
01
02
START/
STOP
*
24 VAC/VDC
(+)
(-)
A3
A1
A2
01
02
START
STOP
*
110-240 VAC (C1 models)
110-240 VAC
(+)
(-)
A3
A1
A2
01
02
START/
STOP
*
110-240 VAC
(+)
(-)
A3
A1
A2
01
02
START
STOP
*
380-440 VAC (C1 models)
A3
A1
A2
01
02
START/
STOP
*
380-440 VAC
380-440 VAC
A3
A1
A2
01
02
START
STOP
*
* Also resets trip states.
4.5 Motor
Thermistor
Motor thermistors (if any) can be connected directly to the TMC7 terminals C1 & C2. If no motor thermistors are connected there must
be a link between C1 & C2.
C1
C2
C1
C2
C1
C2
9
8
9
4.6 Adjustments
Ready
Run
TOSH IBA INTERNATIONAL COR PORATION PTY
LTD - AUSTRALIA
SOFT STARTER
C1
R33 R34
C2
R43R44 02 01 A2 A1 A3
Motor
Thermistor
Input
N.O.
N.O.
Relay Outputs
110 - 240VAC
Control Supply
380 - 440VAC or
Start
Stop
RESET
Aux
Relay
Phase
Rotation
TRIP CODES
Ready
x 1. Power
Circuit
x 2. Excess
Start Time
x 3. Motor
Overload
x 4. Motor
Thermistor
x 5. Current
Imbalance
x 6. Supply
Frequency
x 7. Phase
Rotation
x 8. Comms
Failure
Motor FLC
(% TMC7 FLC)
Current Ramp
(%FLC/Ramp Time)
OFF
5s
15s
15
2s
5s
5s
2s
2s
15
70%
80%
60%
90%
100%
50%
Current Limit
(% Motor FLC)
350%
450%
400%
300%
250%
Motor Trip
Class
OFF
2
4
6
8
10
12
14
16
20
Excess
Start Time
OFF
2s
4s
6s
8s 10s 12s
14s
16s
20s
TMC
7
S ERIES
Soft Stop
(Seconds)
No
Soft Stop
2s
4s
6s
8s 10s 12s
14s
16s
20s
2
3
4
1
Motor Full Load Current
Current Ramp
Current Limit
Motor Trip Class
5
Local Reset Push Button
6
Soft Stop Time
7
Excess Start Time
8
Phase Rotation Protection
9
Auxiliary Relay Function