67
UPS Control for 4200FA/4300
This page shows the adjustable settings of the 4200FA/4300 UPS.
UPS Auto Restart
This field shows the mode at which to enter when UPS is restarted. It can be enabled or disabled. It is set by the
administrator.
0-Disable
1-Enable
UPS Remote Bypass Switch
This field allows the user to remotely transfer the UPS to bypass. It can be enabled or disabled. It is set by the
administrator.
0-Disable
1 – Enable
Note: UPS must be in On-Line mode before this feature can be enabled.
UPS Auto Retransfer
This field shows the present mode for the auto retransfer function of the UPS. It can be enabled or disabled. It is set
by the administrator.
0 - Disable
1 - Enable
Battery Auto Test
This field shows the present status for the UPS battery auto test function. It can be enabled or disabled. It is set by the
administrator.
0 - Disable
1 - Enable
Battery Auto Test Interval
This field shows the test interval at which UPS should automatically test the batteries. It can be set daily, weekly, or
monthly. It is set by the administrator.
0 - Daily
1 - Weekly
2 - Monthly
Battery Test at Start Up
This field shows the present mode for the UPS battery test at startup function. It can be enabled or disabled. It is set
by the administrator.
0 - Disable
1 - Enable
Battery Power Fail Equalize Duration (secs)
This field shows the minimum amount of time, in seconds, required for the UPS to remain in battery backup mode
before it will trigger equalize charge mode.
Range - 60 to 315 seconds
Battery Start Equalize Charge
This field shows the present mode of the UPS Battery Start Equalize Charge function. It can be enabled or disabled.
It is set by the administrator.
0 - Disable
1 - Enable