RemotEye III User Manual – 62330-005
87
This table lists the detail history of operation mode changes that has occurred on the UPS. The Log can store a
maximum of 680 records. If more events are recorded, the new record replaces the oldest record.
1600XP Operation Mode Records Log Format
•
Log Date – This field shows the date of the recording.
•
Log Time - This field shows the time that the values were recorded. Time is displayed in the hh:mm:ss 24-
hour format (i.e., 8:30 p.m. is 20:30:00).
•
Record Number - Maximum number of records is 255.
•
System Input Type
•
System Output Type
•
Input Voltage (%)
•
Output Voltage (%)
•
Output Load (%)
•
DC Input Voltage (%)
•
Battery Voltage (%)
•
From
•
To
•
Branch (Used for Technical Support)
•
Cause (Used for Technical Support)
4200FA/4300 Operation Mode Records Log Format
•
Log Date – This field shows the date of the recording.
•
Log Time - This field shows the time that the values were recorded. Time is displayed in the hh:mm:ss 24-
hour format (i.e., 8:30 p.m. is 20:30:00).
•
Record Number – Maximaum Number of records is 255.
•
Next – State of the UPS.
o
•
Condition 1: List of possible conditions:
conditions:
o
Input voltage undervoltage
o
Input voltage overvoltage
o
Input voltage out of spec
o
Bypass Voltage Undervoltage
o
Bypass Voltage Overvoltage
o
Output Voltage Undervoltage
o
Output Voltage Overvoltage
o
DC Bus Undervoltage
•
Condition 2: List of possible conditions:
o
DC bus out of spec
o
Battery Voltage low
o
Battery voltage reached shutdown level
o
Power Failure
o
DC Bus low
o
Battery voltage out of spec
List of
•
Status: List of possible conditions:
o
Input Frequency Detection
o
Input Phase Rotation Error
o
Input Frequency Error