162
RemotEye III User Manual – 62330-005
Registers Data Type
Size
Description
Units
Comments
Ba
tt
er
y
Te
st
10020
Discrete
1-Bit
Battery Test Disabled
True/False (1/0)
10021
Discrete
1-Bit
Battery Test in Progress
True/False (1/0)
10022
N/A
N/A
N/A
N/A
10023
N/A
N/A
N/A
N/A
N
/A
10024
N/A
N/A
N/A
N/A
N
/A
10025
N/A
N/A
N/A
N/A
10026
N/A
N/A
N/A
N/A
EMD
10027
Discrete
1-Bit
EMD Enabled
True/False (1/0)
10028
Discrete
1-Bit
EMD Alarm-1
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
10029
Discrete
1-Bit
EMD Alarm-2
True/False (1/0)
0 = no Alarm; 1 = Alarm Triggered
F
a
u
lts
10030
Discrete
1-Bit
General Alarm Fault
True/False (1/0)
0 = No Faults, 1 = One or more fault reported, see
below for cause;
10031
Discrete
1-Bit
Open Fuse Fault
True/False (1/0)
10032
Discrete
1-Bit
Current Limit Fault
True/False (1/0)
10033
N/A
N/A
N/A
N/A
10034
Discrete
1-Bit
DC Bus Overcurrent Fault
True/False (1/0)
10035
Discrete
1-Bit
DC Bus Overvoltage Fault
True/False (1/0)
10036
Discrete
1-Bit
DC Bus Imbalance Fault
True/False (1/0)
10037
Discrete
1-Bit
DC Bus Under Voltage During Boost-
up Fault
True/False (1/0)
10038
Discrete
1-Bit
DC Bus Under Voltage During
Charging Fault
True/False (1/0)
10039
Discrete
1-Bit
Charger Overvoltage Fault
True/False (1/0)
10040
Discrete
1-Bit
Output Under Voltage Fault
True/False (1/0)
10041
Discrete
1-Bit
Output Overvoltage Fault
True/False (1/0)
10042
Discrete
1-Bit
Heatsink Overheat Fault
True/False (1/0)
10043
Discrete
1-Bit
UPS Overload Fault
True/False (1/0)
10044
N/A
N/A
N/A
N/A
N/A
10045
N/A
N/A
N/A
N/A
N/A