– 75 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[F04]
[Discharge temp. sensor (TD) trouble]
Is connection of CN603 correct?
Is resistance value of TD sensor correct?
YES
NO
Correct connector.
Replace TD sensor
Check control P.C. board.
Failure
→
Replace
[F06]
[Heat exchanger temp. sensor (TE) trouble]
Is connection of CN601 correct?
Is resistance value of TE sensor correct?
YES
NO
Correct connector.
Replace TE sensor
Check control P.C. board.
Failure
→
Replace
[F07]
[Heat exchanger temp. sensor (TL) trouble]
Is connection of CN604 correct?
Is resistance value of TL sensor correct?
YES
NO
Correct connector.
Replace TL sensor
Check control P.C. board.
Failure
→
Replace
[F12]
[Suction temp. sensor (TS) trouble]
Is connection of CN600 correct?
Is resistance value of TS sensor correct?
YES
NO
Correct connector.
Replace TS sensor
Check control P.C. board.
Failure
→
Replace
[F08]
[Outside temp. sensor (TO) trouble]
Is connection of CN602 correct?
Is resistance value of TO sensor correct?
YES
NO
Correct connector.
Replace TO sensor
Check control P.C. board.
Failure
→
Replace
[F13]
[Heat sink temp. sensor (TH) trouble]
Check compressor IPDU P.C. board.
Failure
→
Replac
* When replacing Compressor IPDU P.C.board,
replace the fuse.