– 18 –
Concealed Duct Type
Installation Manual
EN
Concealed Duct Type
Installation Manual
10
Maintenance
<Daily maintenance>
▼
Cleaning of air filter
• If
is displayed on the remote controller, maintain the air
filter.
1
Push the
button to stop the operation, then
turn off the circuit breaker.
After the cooling or dry operation, the fan keeps
running for self-cleaning. Push the
button
twice to stop the operation.
1. Take out the air filter.
• Slide the knob on the air inlet panel in the direction of the arrow, then open the panel downward.
Rotate the clamp on the lower part of the unit, then remove the air filter.
2. Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid water with neutral detergent or water.
• After cleaning with water, dry the air filter sufficiently in a shade place.
3. Mount the air filter.
2
Turn on the circuit breaker, then push the
button on the remote controller to start the
operation.
3
After cleaning, push
.
display disappears.
CAUTION
• Do not start the air conditioner while leaving air filter removed.
• Push the filter reset button. (
indication will be turn off.)
3
1,2
Hold the frame to
pull out
downward.
Knob
Open
▼
Periodic Maintenance
• For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air
conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor
unit at least once every 3 months. Ask a professional for this cleaning/maintenance work.
Such maintenance can extend the life of the product though it involves the owner’s expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage,
and even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
▼
Maintenance List
Parts
Inspection method
Heat exchanger
Access from inspection opening and remove the access panel. Examine the heat exchanger if there
is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Fan
Access from inspection opening and remove the access panel. Examine the fan if there are any
waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the filter.
Drain pan
Access from inspection opening and remove the access panel. Check if there is any clogging or drain
water is polluted.
Part
Unit
Check (visual/auditory)
Maintenance
Heat exchanger
Indoor/outdoor
• Dust/dirt clogging, scratches
• Wash the heat exchanger when it is
clogged.
Fan motor
Indoor/outdoor
• Sound
• Take appropriate measures when
abnormal sound is generated.
Filter
Indoor
• Dust/dirt, breakage
• Wash the filter with water when it is
contaminated.
• Replace it when it is damaged.
Fan
Indoor
• Vibration, balance
• Dust/dirt, appearance
• Replace the fan when vibration or
balance is terrible.
• Brush or wash the fan when it is
contaminated.
Air inlet/outlet grilles
Indoor/outdoor
• Dust/dirt, scratches
• Fix or replace them when they are
deformed or damaged.
Drain pan
Indoor
• Dust/dirt clogging, drain
contamination
• Clean the drain pan and check the
downward slope for smooth drainage.
Ornamental panel,
louvres
Indoor
• Dust/dirt, scratches
• Wash them when they are contaminated
or apply repair coating.
Exterior
Outdoor
• Rust, peeling of insulator
• Peeling/lift of coat
• Apply repair coating.
35-EN
36-EN
+00EH99878599_01EN.book Page 18 Saturday, April 2, 2011 4:13 PM