Concealed Duct Type
Installation Manual
EN
Concealed Duct Type
Installation Manual
– 6 –
4
Installation
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only.
Do not apply force to the other parts (such as refrigerant pipe, drain pan, foamed parts, or resin parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
External Dimensions
(Unit: mm)
▼
Dimension
A
B
C
D
E
F
G
H
J
K
M
N
SM56 type
700
766
690
750
780
12.7
6.4
252
280
280
1
2
SM80 type
1000
1066
990
1050
1080
15.9
9.5
252
580
290
2
3
SM100, SM140 type
1350
1416
1340
1400
1430
15.9
9.5
252
930
310
2
4
110
129
44
49
59
41
75
J = M x K
H
60~260
9
C
41
196
393
498
638
50
131
243
50
174
320
Knock-out hole Ø125
(Air take-in port)
Discharge port flange
N-Ø200
Hanging bolt pitch B
Main unit dimension A
Hanging bolt
4-M10 screw
(Arranged locally)
Refrigerant pipe connecting port
(Gas side ØF)
Main unit dimension 800
Hanging bolt pitch 700
Drain pipe
connecting port
for vinyl chloride
pipe (Inner dia.
32, VP. 25)
Suction port
flange (Procured
locally)
Suction port
panel
(Procured
locally)
Ø26 Power supply,
remote controller
wire take-out port
Ceiling open size 470
Panel external dimension 500
Refrigerant
pipe
connecting
port (Liquid
side ØG)
Ceiling open size D
Panel external dimension E
Suction port canvas
(Procured locally)
6-Ø4
Tapping screw
undersized hole Ø160
Panel C.L
410
Installation of hanging bolt
• Consider the piping/wiring after the unit is hung to
determine the location of the indoor unit installation
and orientation.
• After the location of the indoor unit installation has
been determined, install hanging bolts.
• For the dimensions of the hanging bolt pitches, refer
to the external view.
• When a ceiling already exists, lay the drain pipe,
refrigerant pipe, control wires, and remote controller
wires to their connection locations before hanging
the indoor unit.
Procure hanging bolts washer and nuts for installing
the indoor unit (these are not supplied).
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, to be local procure).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
Installation of indoor unit
Treatment of ceiling
The ceiling differs according to structure of building.
For details, consult your constructor or interior finish
contractor.
In the process after the ceiling board has been
removed, it is important to reinforce ceiling foundation
(frame) and to keep horizontal level of installed ceiling
correctly in order to prevent vibration of ceiling board.
• Attach the nuts and the M10 flat washers to the
hanging bolt.
• Put washers at up and down of the hanging bracket
of the indoor unit to hang down the indoor unit.
• Check that four sides are horizontal with a level
gauge. (Horizontal degree: Within 5mm)
REQUIREMENT
• Hang the unit in a horizontal position.
When unit is hanged to slant, it may cause overflow of
drainage.
• Install the unit within the dimension according to the
figure below.
• Use level guage to confirm whether the unit is hang
horizontally.
Hanging bolt
M10 or W3/8
4 pieces
Nut
M10 or W3/8
12 pieces
Washer
M10
8 pieces
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Steel flame structure
Use existing angles or install new support angles.
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Rubber
Anchor bolt
(Blade type
bracket)
(Slide type
bracket)
(Pipe hanging
anchor bolt)
Hanging bolt
Hanging bolt
Support angle
Nut
(W3/8 or M10)
M10 flat washer
M10 flat washer
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
0 to 5mm
±5mm
Set the air inlet and air outlet
sides are within 5mm with each
other.
Set the drain pipe connecting
port side within 5mm lower
than opposite side.
Front view
Side view
11-EN
12-EN