Concealed Duct Type

Installation Manual

EN

Concealed Duct Type

Installation Manual

– 6 –

4

Installation

CAUTION

Strictly comply with the following rules to prevent damage of the indoor units and human injury.

• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering 

cloth or other material to not damage the unit.

• To move the indoor unit, hold the hooking brackets (4 positions) only.

 

Do not apply force to the other parts (such as refrigerant pipe, drain pan, foamed parts, or resin parts).

• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.

„

External Dimensions

(Unit: mm)

Dimension

A

B

C

D

E

F

G

H

J

K

M

N

SM56 type

700

766

690

750

780

12.7

6.4

252

280

280

1

2

SM80 type

1000

1066

990

1050

1080

15.9

9.5

252

580

290

2

3

SM100, SM140 type

1350

1416

1340

1400

1430

15.9

9.5

252

930

310

2

4

110

129

44
49

59

41

75

J = M x K

H

60~260

9

C

41

196

393

498

638

50

131

243

50

174

320

Knock-out hole Ø125  

(Air take-in port)

Discharge port flange 

N-Ø200

Hanging bolt pitch B

Main unit dimension A

Hanging bolt 

4-M10 screw 

(Arranged locally)

Refrigerant pipe connecting port 

(Gas side ØF)

Main unit dimension 800

Hanging bolt pitch 700

Drain pipe 

connecting port 

for vinyl chloride 

pipe (Inner dia. 

32, VP. 25)

Suction port 

flange (Procured 

locally)

Suction port 

panel 

(Procured 

locally)

Ø26 Power supply, 

remote controller  

wire take-out port

Ceiling open size 470

Panel external dimension 500

Refrigerant 

pipe 

connecting 

port (Liquid 

side ØG)

Ceiling open size D

Panel external dimension E

Suction port canvas 

(Procured locally)

6-Ø4 

Tapping screw 

undersized hole Ø160

Panel C.L 

410

„

Installation of hanging bolt

• Consider the piping/wiring after the unit is hung to 

determine the location of the indoor unit installation 
and orientation.

• After the location of the indoor unit installation has 

been determined, install hanging bolts.

• For the dimensions of the hanging bolt pitches, refer 

to the external view.

• When a ceiling already exists, lay the drain pipe, 

refrigerant pipe, control wires, and remote controller 
wires to their connection locations before hanging 
the indoor unit.

Procure hanging bolts washer and nuts for installing 
the indoor unit (these are not supplied).

Installation of hanging bolt

Use M10 hanging bolts (4 pcs, to be local procure). 

 

Matching to the existing structure, set pitch according 
to size in the unit external view as shown below.

„

Installation of indoor unit

Treatment of ceiling

The ceiling differs according to structure of building.

 

For details, consult your constructor or interior finish 
contractor.

 

In the process after the ceiling board has been 
removed, it is important to reinforce ceiling foundation 
(frame) and to keep horizontal level of installed ceiling 
correctly in order to prevent vibration of ceiling board.

 

• Attach the nuts and the M10 flat washers to the 

hanging bolt.

• Put washers at up and down of the hanging bracket 

of the indoor unit to hang down the indoor unit.

• Check that four sides are horizontal with a level 

gauge. (Horizontal degree: Within 5mm)

REQUIREMENT

• Hang the unit in a horizontal position.

 

When unit is hanged to slant, it may cause overflow of 
drainage.

• Install the unit within the dimension according to the 

figure below.

• Use level guage to confirm whether the unit is hang 

horizontally. 

Hanging bolt

M10 or W3/8

4 pieces

Nut

M10 or W3/8

12 pieces

Washer

M10

8 pieces

New concrete slab

Install the bolts with insert brackets or anchor bolts.

Steel flame structure

Use existing angles or install new support angles.

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

Rubber

Anchor bolt

(Blade type 

bracket)

(Slide type 

bracket)

(Pipe hanging 

anchor bolt)

Hanging bolt

Hanging bolt

Support angle

Nut

(W3/8 or M10)

M10 flat washer

M10 flat washer

Hanging bolt

(W3/8 or M10)

Nut

(W3/8 or M10)

0 to 5mm

±5mm

Set the air inlet and air outlet 

sides are within 5mm with each 

other.

Set the drain pipe connecting 

port side within 5mm lower 

than opposite side.

Front view

Side view

11-EN

12-EN

+00EH99878599_01EN.book  Page 6  Saturday, April 2, 2011  4:13 PM

Содержание RAV-SM1104BT-E

Страница 1: ... name Concealed Duct Type RAV SM564BT E RAV SM804BT E RAV SM1104BT E RAV SM1404BT E Installation Manual English AIR CONDITIONER SPLIT TYPE Installation Manual 00EH99878599_01EN book Page 1 Saturday April 2 2011 4 13 PM ...

Страница 2: ...tion and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or indivi...

Страница 3: ...Repair of outdoor unit Gloves to provide protection for electricians and from heat Warning Indications on the Air Conditioner Unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get bu...

Страница 4: ...ity of high winds and earthquake If the air conditioner is not installed appropriately a unit may topple over or fall down causing an accident If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may generate Use forklift to carry in the air conditioner units and use winch or hoist at installa...

Страница 5: ...istics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Accompanied with the new refrigerant refrigerating oil has also been changed Therefore during installation work be sure that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle To prevent charging an incorrect ...

Страница 6: ...he equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to dire...

Страница 7: ...on of the indoor unit installation has been determined install hanging bolts For the dimensions of the hanging bolt pitches refer to the external view When a ceiling already exists lay the drain pipe refrigerant pipe control wires and remote controller wires to their connection locations before hanging the indoor unit Procure hanging bolts washer and nuts for installing the indoor unit these are n...

Страница 8: ...ipe provide support brackets at intervals of 1 5 to 2 meters to prevent flapping Install the collective piping as shown in the following figure Do not provide any air vents Otherwise the drain water will spout causing water to leak Do not allow any force to be applied to the connection area with the drain pipe Pipe material size and insulator The following materials for piping work and insulating ...

Страница 9: ...heck whether the water is draining from the drain pipe connecting port and check that no water is leaking from the drain pipe After checking that the water drains and there are no water leaks turn off the power connect the float switch connector to its original location CN34 on the printed circuit board and return the electrical parts box to its original position When a down gradient cannot be sec...

Страница 10: ...y cause not only a gas leak but also a trouble of the refrigeration cycle CAUTION Tightening with an excessive torque may crack the nut depending on installation conditions Evacuation Perform vacuuming from the charge port of valve of the outdoor unit by using a vacuum pump For details follow to the Installation Manual attached to the outdoor unit Do not use the refrigerant sealed in the outdoor u...

Страница 11: ...er unit wiring L L1 L2 Ln In case of wired type only Up to 500m In case of wireless type included Up to 400m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200m A B L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller Max 8 units Remote controller wiring Wiring between Indoor Unit and Outdoor Unit 1 Figure below s...

Страница 12: ...he outdoor interface circuit board While the automatic addresses are being set up no remote controller operations can be performed Setup takes up to 10 minutes usually about 5 minutes When the power is turned on after automatic address setup It takes up to 10 minutes usually about 3 minutes for the outdoor unit to start operating after the power has been turned on Before the air conditioner was sh...

Страница 13: ...High static pressure 2 0006 20Pa Low static pressure Installing optional filters Make Filter setting when optional filters are installed Follow to the basic operation procedure 1 2 3 4 5 6 For the CODE No in Procedure 3 specify 5d As the SET DATA in procedure 4 select the SET DATA of the filter installed from the following table With a remote controller less system group control Besides the switch...

Страница 14: ...ng button 5 Push button to complete the setting SET DATA Filter sign term 0000 None 0001 150H 0002 2500H Factory default 0003 5000H 0004 10000H SET DATA Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C UNIT No 1 1 UNIT No 1 2 UNIT No 1 3 UNIT No 1 4 Setting of power level in power saving mode Remote controller switch monitoring f...

Страница 15: ... indoor units by wiring the inter unit wire of the remote controller When the power supply has been turned on the automatic address setup starts and which indicates that address is being set up flashes on the display part in about 3 minutes During setup of automatic address the remote controller operation is not accepted Required time up to the finish of automatic addressing is approx 5 minutes NO...

Страница 16: ...3 3 2 4 2 5 2 5 3 Display changes according to the model No of indoor unit Indoor UNIT No before setup change is displayed Indoor UNIT No before setup change is displayed 5 1 Specify CODE No 14 TEMP buttons CODE No 14 Group address 2 Change the SET DATA from 0001 to 0002 TIME buttons SET DATA Header unit 0001 Follower unit 0002 3 Push button In this time the setup finishes when the display changes...

Страница 17: ... the remote controller is not accepted for approx 1 minute 2 1 3 1 Display changes according to the model No of indoor unit 8 C Operation SDI series4 and DI series4 only Pre heating operation can be set for cold regions where room temperature drops to below zero 1 Push buttons simultaneously for 4 seconds or more when the air conditioner is not working After a while the display part flashes as sho...

Страница 18: ...2 4 3 1 5 Wireless remote controller 1 Remove the small screw which fixes the nameplate of the receiver unit Remove the nameplate of the sensor section by inserting a minus screwdriver etc into the notch at the bottom of the plate and set the Dip switch to TEST RUN ON 2 Execute a test operation with ON OFF button on the wireless remote controller and LED flash during test operation Under status of...

Страница 19: ...ntenance work Such maintenance can extend the life of the product though it involves the owner s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance List Parts Inspectio...

Страница 20: ... indoor unit and outdoor unit Auto reset IPDU CDB communication error E08 Duplicated indoor addresses Indoor Indoor address setting error The same address as the self address was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting error Two remote controllers are set as header in the double remote controller control The header indoor uni...

Страница 21: ...detected in the discharge temp releasing control Entire stop P04 ALT Outdoor unit high pressure system error Outdoor High pressure switch The IOL was activated or an error was detected in the high pressure releasing control using the TE Entire stop P05 ALT Open phase detected Outdoor The power wire may be connected incorrectly Check open phase and voltages of the power supply Entire stop P07 ALT H...

Страница 22: ...EH99878599 00EH99878599_01EN book Page 51 Saturday April 2 2011 4 13 PM ...

Отзывы: