Concealed Duct Type
Installation Manual
EN
Concealed Duct Type
Installation Manual
– 12 –
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3
Specify CODE No. [
] with “TEMP.”
/
buttons.
4
Select SET DATA [
] with “TIME”
/
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
2
.
• To change other settings of the selected indoor
unit, repeat from Procedure
3
.
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
Procedure
2
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes
and then the display content disappears and
the air conditioner enters the normal stop
mode.
(While
is flashing, no operation of the
remote controller is accepted.)
External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• Specify [5d] to the CODE No. in procedure
3
.
• For the SET DATA of procedure
4
, select a SET
DATA of the external static pressure to be set up
from the following table.
<Change on wired remote controller>
*
1
: 65Pa for SM1404
*
2
: 90Pa for SM1404
SET DATA
External static pressure
0000
40Pa
Standard (Factory default)
0001
70Pa *
1
High static pressure 1
0003
100Pa *
2
High static pressure 2
0006
20Pa
Low static pressure
Installing optional filters
Make Filter setting when optional filters are installed.
• Follow to the basic operation procedure (
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [5d].
• As the SET DATA in procedure
4
, select the SET DATA of the filter installed from the following table.
With a remote controller-less system (group control)
Besides the switching method using the wired remote controller as a way to establish the external static pressure
and filter settings, these settings can be changed by arranging the jumper block on the indoor unit micro computer
P.C. board as shown in the following table as well.
* However, once the setting is changed, it is necessary to reset the SET DATA to 0000 that placing the jumper
block back to the factory default position and rewriting the SET DATA back to 0000 with wired remote controller
(sold separately).
• Change over the jumper blocks on the indoor P.C. board, and select the desired setting.
Jumper block positions (CN112, CN111 and CN110 from the left)
* When the High-efficiency filter 65 or 90 is used, resistance of about 30 Pa is applied. Adjust the duct resistance
(external static pressure) of the duct to 40 Pa.
SET DATA
Filter
0000
Standard filter (Factory default)
0001
High-efficiency filter 65
High-efficiency filter 90
Jumper block
position
SET DATA
0000
0001
0003
0006
External static
pressure
40 Pa
70 Pa
100 Pa
20 Pa
Standard
(Factory default)
High static Pressure 1
High static Pressure 2
Low static Pressure
Filter
Standard filter
(Factory default)
High-efficiency filter 65
High-efficiency filter 90
—
—
Short
Open
CN112 CN111 CN110
CN112 CN111 CN110
CN112 CN111 CN110
CN112 CN111 CN110
23-EN