![Toshiba RAV-GP1101AT8-E Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/toshiba/rav-gp1101at8-e/rav-gp1101at8-e_service-manual_1135210026.webp)
– 26 –
1. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for piping whose outer diameter exceeds 20
mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6-2-5 below.
b) Socket Joints
Socket joints are such that they are braced for connections, and used mainly for thick piping whose
diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 6-2-2.
Table 6-2-1 Thickne
ss
e
s
of annealed copper pipe
s
Nominal diameter
1/4
3
/
8
1/2
5/
8
Outer diameter (mm)
6.4
9
.5
12.7
15.
9
Thickne
ss
(mm)
R410A or R32
R22
0.
8
0
0.
8
0
0.
8
0
0.
8
0
0.
8
0
0.
8
0
1.00
1.00
Table 6-2-2 Minimum thickne
ss
e
s
of
s
ocket joint
s
Nominal diameter
1/4
3
/
8
1/2
5/
8
Reference outer diameter of
copper pipe jointed (mm)
6.4
9
.5
12.7
15.
9
Minimum joint thickne
ss
(mm)
0.50
0.60
0.70
0.
8
0
6-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not
enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used,
and that refrigerant does not leak.
When using lubricating oils in the piping processing, use such lubricating oils whose water content has been
removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur.
Carefully remove all burrs and clean the cut surface before installation.
Содержание RAV-GP1101AT8-E
Страница 23: ... 23 4 WIRING DIAGRAM 4 1 Outdoor Unit RAV GP1101AT8 J E TR RAV GP1401AT8 J E TR RAV GP1601AT8 J E TR ...
Страница 103: ... 103 Outdoor Unit RAV GP1401AT8 E RAV GP1401AT8J E RAV GP1401AT8 TR RAV GP1401AT8J TR ...
Страница 105: ... 105 Outdoor Unit RAV GP1601AT8 E RAV GP1601AT8J E RAV GP1601AT8 TR RAV GP1601AT8J TR ...