Unit Installation –
UH/U UNITS
Check the dimensions of the unit illustrated in the
following figure. Use the accompanying template for
installation and adjust the position of the body of the
unit to the position of the opening on the ceiling.
Secure the cardboard template to the body of the
indoor unit with four bolts (M5 x 20mm).
!
!
Installing Ø 10 Hanging Bolts (4 pieces)
l
Install the hanging bolts at the intervals shown in the
following figure.
l
Use Ø 10 hanging bolts (to be locally procured).
Ceiling preparation: The actual procedure differs according
to the structure. Consult your builder or whoever was
responsible for the interior of the house/building.
(1)
Removal of part of the ceiling plate:
In order to ensure that the ceiling is kept perfectly
horizontal and to prevent the ceiling from vibrating the
ceiling framework must be reinforced;
(2) Cut and remove part of the ceiling framework;
(3) Reinforce the ends of the ceiling framework where it was
cut and add framework to secure the ends.
l
Some piping and wiring connections must be made in the
ceiling after the unit has been suspended. After selecting where
the unit will be installed, decide on the direction of the piping
connection. If the ceiling is already installed, prepare the
refrigerant pipe, drain pipe, indoor to outdoor unit connection
wiring and the remote control cord at the piping and wiring
connection positions before suspending the indoor unit.
Installation on a steel frame:
Use the angular
bracket in the
structure or install
one for support.
Cross
length
of wood
Hanging
bolt
Beam
Ceiling
Installation on a wooden structure:
Place a length of wood of the appropriate size across two
beams and install the hanging bolts into this length of wood.
Installation on an existing concrete slab:
Use hole-in anchors, hole-in plugs
or hole-in bolts for the installation.
How to Install the Hanging Bolts
Installation on a newly installed concrete slab:
Use insert brackets or foundation bolts for the installation.
Knife-shaped
bracket
Sliding
bracket
Reinforcing
bar
Foundation
bolt
(Foundation bolt for
hanging the piping)
Hanging
bolt
Angular
bracket for
support
Hanger bolt
RAV-164UH/U
RAV-264UH/U
880 (CEILING OPENING)
Wiring connection (Gland
Plate 3 x Ø20 holes)
Drain pipe connection
(1'' BSP threaded connection)
940 (PANEL DIMENSION)
Drain Pipe
(1'' BSP Threaded Connection)
820 (EXTERNAL CASSETTE DIMENSION)
800 HANGER BOL
T
PITCH
820 (EXTERNAL
DIMENSION PITCH)
880 (CEILING OPENING)
940 (P
ANEL
DIMENSION)
Fresh Air Inlet
620 (HANGER BOLT PITCH)
Refrigerant pipe
connection (Gas ØA)
Refrigerant pipe
connection (Liquid ØB)
Model (RAV-)
164UH/U
264U
264UH
ØA
12.7
15.9
15.9
ØB
6.4
9.5
9.5
I
NDOOR
U
NIT
L
OCATION