When the installation plate is directly
mounted on the wall
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook
up he indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, use the anchor bolt holes as
illustrated in the below figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt holes.
Otherwise the unit may fall down and result in
personal injury and property damage.
Fig. 10-3-4
Fig. 10-3-5
CAUTION
Failure to firmly install the unit may result in
personal injury and/or property damage if the
unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws
.
NOTE :
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
Anchor bolt
Projection
15mm or less
5 mm dia. hole
Clip anchor
(local parts)
5 Mounting screw
Ø4 × 25
l
Installation plate
(Keep horizontal direction.)
10-3-
3
.
Piping and Drain Hose Installation
Piping and drain hose forming
• Since condensation results in machine trouble,
make sure to insulate both the connecting pipes
separately.
(Use polyethylene foam as insulating material.)
Fig. 10-3-7
1. Die-cutting
bush body slit
For Bottom right
Cut out the slit on bottom right side of bush body
for bottom right connection with a pair of nippers.
For Left or Right
Take off Cap and cut out the slit on left or right
side of bush body for the left or right connection
with a pair of nippers.
2. Changing drain hose
For leftward connection's piping, it is necessary
to change the drain hose and dain cap.
Fig. 10-3-8
•
•
Rear right
Rear left
Bottom left
Left
Bottom right
Right
Die-cutting
bush body
slit
T
ake of
f cap
and cut bush
body slit
Changing
drain hose
Piping preparation
Changing
drain
hose
How to remove the drain hose
Heat insulator
Drain hose
•
The drain hose can be removed by removing the
screw securing the drain hose and then pulling out
the drain hose.
•
•
When removing the drain hose, be careful of any
sharp edges of steel plate. The edges can injuries.
To install the drain hose, insert the drain hose firmly
until the connection part contacs with heat insulator,
and then secure it with original screw.
FILE NO. SVM-17050
- 68 -
Содержание RAS-25PAVPG-ND