FILE NO. SVM-13074
How to fix the drain cap
1) Insert a hexagon wrench 3/16 in. (4 mm)
in the center head of the cap.
Fig. 10-
4
-17
2) Firmly insert the drain cap.
Fig. 10-
4
-18
CAUTION
Firmly insert the drain hose and drain cap; otherwise,
water may leak.
<In case of right or left piping>
•
After making slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Fig. 10-
4
-19
<In case of bottom right or bottom left piping>
•
After making slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Fig. 10-
4
-20
Insert a hexagon
wrench
3/16 in
(4 mm)
No gap
Slit
Slit
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap.
Application causes deterioration
and drain leakage
from
the plug.
(
4 mm
)
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 1-5/8 in.
(
43 mm
)
above the wall surface. If the connecting pipe is
laid exceeding 1-5/8 in
(
43 mm
)
above the wall surface,
the indoor unit may
set on the wall unstably.
When
bending the connecting pipe, make sure to use a
spring bender to avoid crushing the pipe.
Fig. 10-
4
-21
NOTE
If the pipe is bent incorrectly, the indoor unit may
set on the wall
unstably.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe
s
to the
refrigerant
line
and wrap facing tape around them.
CAUTION
•
Bind the
refrigerant lines
(two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the
refrigerant lines
(two) only with facing tape.
•
Carefully arrange pipes
such that none of them
stick out the rear plate of the indoor unit.
•
Carefully connect the refrigerant lines and
connecting pipes to
one
another
and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
•
Check for gas leaks before insulating.
Installation plate
Refrigerant lines
Indoor unit
Connecting cable
80
Outward form of indoor unit
R 1-3/16 in. (R 30 mm) (Use polisin
(polyethylene) core or the like for
bending pipe.)
Use the handle of screwdriver, etc.
1-5/8 in. (43 mm)
3/16 in.
Bend the connecti
ng
pipe within a radius of
1-3/16
i
m.
To connect
he pipe after the unit has been installed (figure)
(30 mm.)
(
F
orefront of flare)
Liquid side
Gas side
16
-
9
/16 in.
(
42
0 mm)
20
-
1
/
2
in.
(
52
0 mm)