– 14 –

EN

Check codes and parts to be checked

Check method

On the remote control (Wired remote control, Central control remote control) and the interface P.C. board of the 
outdoor unit (I/F), a check display LCD (Remote control) or 7-segment display (on the outdoor interface P.C. board) 
to display the operation is provided. Therefore the operation status can be known. With this self-diagnosis function, 
a trouble or position with error of the air conditioner can be found as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.
• To check from indoor remote control: See “Wired remote control display” in the list.
• To check from outdoor unit: See “Outdoor 7-segment display” in the list.
• To check from indoor unit with a wireless remote control: See “Sensor block display of receiving unit” in the list.

IPDU : Intelligent Power Drive Unit

: Lighting, 

: Flashing, 

: Goes off

ALT : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

E01

Communication error between indoor and remote 

control 

(Detected at remote control side)

Remote control

E02

Remote control transmission error

Remote control

E03

Communication error between indoor and remote 

control (Detected at indoor side)

Indoor

E04

Communication circuit error between indoor / 

outdoor (Detected at indoor side)

Indoor

E06

E06

No. of indoor units in which 

sensor has been normally 

received

Decrease of No. of indoor units

I/F

E07

Communication circuit error between indoor / 

outdoor (Detected at outdoor side)

I/F

E08

E08 Duplicated indoor addresses

Duplicated indoor addresses

Indoor / I/F

E09

Duplicated header remote controls

Remote control

E10

Communication error between indoor MCU

Indoor

E12

E12

01: Indoor / Outdoor 

communication

02: Communication between 

outdoor units

Automatic address start error

I/F

E15

E15

Indoor is nothing during automatic addressing

I/F

E16

E16 00: Capacity over

01 ~:No. of connected units

Capacity over / No. of connected indoor units

Combined capacity of indoor units exceeds 120% of 

combined capacity of outdoor units.

I/F

E18

Communication error between indoor units

Indoor

E19

E19 00: Header is nothing

02: Two or more header units

Outdoor header units quantity error

I/F

E20

E20

01: Outdoor of other line 

connected

02: Indoor of other line connected

Other line connected during automatic

address

I/F

E23

E23

Sending error in communication between

outdoor units

I/F

E25

E25

Duplicated follower outdoor addresses

I/F

E26

E26 No. of outdoor units which 

received signal normally

Decrease of No. of connected outdoor units

I/F

E28

E28 Detected outdoor unit number

Follower outdoor unit error

I/F

E31

E31

IPDU communication error

I/F

F01

ALT Indoor TCJ sensor error

Indoor

F02

ALT Indoor TC2 sensor error

Indoor

F03

ALT Indoor TC1 sensor error

Indoor

F04

F04

ALT TD1 sensor error

I/F

F05

F05

ALT TD2 sensor error

I/F

F06

F06 TE1 sensor

TE2 sensor

ALT TE1 sensor error

TE2 sensor error

I/F

F07

F07

ALT TL sensor error

I/F

F08

F08

ALT TO sensor error

I/F

F10

ALT Indoor TA sensor error

Indoor

F12

F12

ALT TS1 sensor error

I/F

F13

F13

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side 

ALT TH sensor error

IPDU

F15

F15

ALT Outdoor temp. sensor miswiring (TE1, TL)

I/F

F16

F16

ALT Outdoor pressure sensor miswiring (Pd, Ps)

I/F

F22

F22

ALT TD3 error

I/F

F23

F23

ALT Ps sensor error

I/F

F24

F24

ALT Pd sensor error

I/F

F29

SIM Indoor other error

Indoor

F31

F31

SIM Indoor EEPROM error

I/F

H01

H01

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Compressor break down

IPDU

H02

H02

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Compressor trouble (lock)

IPDU

H03

H03

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Current detect circuit system error

IPDU

H05

H05

TD1 miswiring

I/F

H06

H06

Low pressure protective operation

I/F

H07

H07

Oil level down detective protection

I/F

H08

H08

01: TK1 sensor error

02: TK2 sensor error

03: TK3 sensor error

04: TK4 sensor error

Oil level detective temp sensor error

I/F

H15

H15

TD2 miswiring

I/F

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

A3-IPDU

Fan 

IPDU

1

2

3

01

02

03

04

05

06

07

08

09

0A

0B

0C

0D

0E

0F

 : IPDU error

27-EN

28-EN

+00EB99808701-1_01EN.book  Page 14  Thursday, June 23, 2016  11:57 AM

Содержание MML-AP0074H2UL

Страница 1: ...al use Pour usage commercial Indoor Unit Model name Floor Console Exposed Type MML AP0074H2UL MML AP0094H2UL MML AP0124H2UL MML AP0154H2UL MML AP0184H2UL MML AP0244H2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EB99808701 1_01EN book Page 1 Thursday June 23 2016 11 57 AM ...

Страница 2: ...ctric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes wa...

Страница 3: ...re the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner CAUTION This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Acco...

Страница 4: ...eyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adver...

Страница 5: ...oor installation Front panel screws Front panel Hock Hock Hock Hock Fan guard Air intake grille External dimensions Unit in mm 10 2 260 9 1 230 27 2 690 37 4 950 24 8 630 6 1 155 9 4 240 7 9 200 1 4 35 5 2 133 17 3 440 2 2 57 5 1 130 1 2 30 1 4 35 2 8 70 3 8 97 2 0 50 4 7 120 27 6 700 20 5 520 3 9 100 2 4 61 1 3 34 10 2 258 7 5 190 4 3 110 1 1 27 7 0 177 4 2 106 6 4 162 1 4 35 5 9 150 1 3 33 5 1 1...

Страница 6: ...2 2 57 20 5 520 Mount the upper two nuts as shown in the figure below Tighten the lower two nuts after the unit has been mounted 0 04 to 0 08 1 to 2 0 6 15 MAX Screwdriver Knockout hole 5 9 150 15 7 400 10 8 275 Rear Anchor bolts two at left and right Front 2 3 7 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained A...

Страница 7: ...rvals of 8 2 to 9 10 2 5 to 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated Use the flare nut attached with the indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Unit in mm Connecting refrigerant piping Flaring 1 Cut th...

Страница 8: ...o gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements If incorrect incomplete wiring is...

Страница 9: ...p to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION Do not put the remote control wires and power supply wires AC208 230 V in the same conduit Doing so may cause trouble in the control system due to noise...

Страница 10: ...as per the Installation Manual supplied with the outdoor unit L2 L1 B A Indoor Outdoor control wire Remote control terminal block Power supply terminal block Electrical control box Ground screw Cord clamp Power supply wire Remote control wire Control wire between indoor and outdoor units L1 L2 0 8 20 1 2 30 0 4 10 Ground wire 0 08 2 or less Power supply wires and control wire A B A B Terminal bloc...

Страница 11: ...yed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be confirmed 3 Specify CODE No with TEMP buttons 4 Select SE...

Страница 12: ...ddress setup refer to the Installation Manual attached to the outdoor unit SET DATA 0000 0001 Remote control sensor Not used Factory default Used 9 How to change the discharge port The air discharging direction of the indoor unit has been set to forward direction as factory default However it is possible to change to upward direction Change the discharging direction according to conditions of the ...

Страница 13: ...eration stops by turning the thermostat OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices Wired remote control 1 Push button for 4 seconds or more TEST is displayed on the display part a...

Страница 14: ...y part of the remote control The error code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurs on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up to 4 errors The log can be...

Страница 15: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Страница 16: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Страница 17: ...refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No pa...

Страница 18: ...0H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANG...

Отзывы: