• Use the tightening torque levels as listed in the 

following table.

• Tightening torque of flare pipe connections.

Pressure of R410A is higher than that of R22. 
(Approx. 1.6 times) Therefore, using a torque 
wrench, tighten the flare pipe connecting sections 
which connect the indoor and outdoor units of the 
specified tightening torque.
Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.

CAUTION

Tightening with an excessive torque may crack the nut 
depending on installation conditions.

Airtight test / air purge, etc.

For air tightness test, adding refrigerant, refer to the 
Installation Manual attached to the outdoor unit.

CAUTION

Do not supply power to the indoor unit until the airtight 
test and vacuuming are completed. (If the indoor unit is 
powered on, the pulse motor valve is fully closed, which 
extends the time for vacuuming.)

Open the valve fully

Open the valve of the outdoor unit fully.

Heat insulation process

Apply heat insulation for the pipes separately at liquid 
side and gas side.
• For the heat insulation to the pipes at gas side, use 

the material with heat-resisting temperature 248 °F 
(120 °C) or higher.

• To use the attached heat insulation pipe, apply the 

heat insulation to the pipe connecting section of the 
indoor unit securely without gap.

REQUIREMENT

Insulate the refrigerant pipe in the indoor unit securely up 
to the point shown in the following figure.

Outer dia. of connecting 

pipe (in (mm))

Tightening torque

(ft•lbs (N•m))

1/4" (6.4)

10 to 13 (14 to 18)

3/8" (9.5)

24 to 31 (33 to 42)

1/2" (12.7)

37 to 46 (50 to 62)

5/8" (15.9)

46 to 57 (63 to 77)

Adhesive tape

Heat insulator 

(accessory)

Heat insulator

Gas pipe

Liquid pipe

7

Electrical connection

WARNING

1.

Use predefined wire and connect them certainly. 
Keep the connecting terminal free from external 
force.

Improper wire connection or clamping may result in 
exothermic, fire or malfunction.

2.

Connect ground wire. (grounding work)

Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water 
pipes, lightning rods or ground wires for telephone 
wires.

3.

Install appliance in accordance with national 
wiring regulations.

Capacity shortage of circuit breaker or incomplete 
installation may cause an electric shock or a fire.

CAUTION

• Consult local building codes, NEC (National Electrical 

Code) or CEC (Canadian Electrical Code) for special 
requirements.

• If incorrect / incomplete wiring is carried out, it will 

cause an electrical fire or smoke.

• If circuit breaker is not installed, an electric shock may 

be caused.

• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and 

inner insulator of power and control wires when 
peeling them.

• Use the power cord and control wire of specified 

thickness, type, and protective devices required.

• Do not connect 208 / 230 V power to the terminal 

blocks (U1, U2, A, B etc.) for control wiring.
(Otherwise, the system will fail.)

• Perform the electric wiring so that it does not come to 

contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.

• Do not turn on the circuit breaker of the indoor unit 

until vacuuming of the refrigerant pipes is completed.

REQUIREMENT

• For power supply wiring, strictly conform to the Local 

Regulation in each country.

• Run the refrigerant piping line and control wiring line in 

the same line.

Power supply wire and 
control wires specifications

Power supply wire and control wires are locally 
procured.
For the power supply specifications, follow the table 
below. If the capacity is too low, overheat or seizure 
may occur.

Indoor unit power supply

For the power supply of the indoor unit, prepare the 
exclusive power supply separated from that of the 
outdoor unit.

Power supply

Control wiring, Central control wiring

• 2-core with non-polarity wires are used for the 

control wiring between indoor unit and outdoor unit 
and Central control wiring.

• To prevent noise trouble, use 2-core shielded wire.
• The length of the communication line means the total 

length of the control wire length between indoor and 
outdoor units added with the central control wire 
length.

Power supply

208 / 230-1-60

13-EN

14-EN

+00EB99808701-1_01EN.book  Page 7  Thursday, June 23, 2016  11:57 AM

Содержание MML-AP0074H2UL

Страница 1: ...al use Pour usage commercial Indoor Unit Model name Floor Console Exposed Type MML AP0074H2UL MML AP0094H2UL MML AP0124H2UL MML AP0154H2UL MML AP0184H2UL MML AP0244H2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EB99808701 1_01EN book Page 1 Thursday June 23 2016 11 57 AM ...

Страница 2: ...ctric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes wa...

Страница 3: ...re the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner CAUTION This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Acco...

Страница 4: ...eyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adver...

Страница 5: ...oor installation Front panel screws Front panel Hock Hock Hock Hock Fan guard Air intake grille External dimensions Unit in mm 10 2 260 9 1 230 27 2 690 37 4 950 24 8 630 6 1 155 9 4 240 7 9 200 1 4 35 5 2 133 17 3 440 2 2 57 5 1 130 1 2 30 1 4 35 2 8 70 3 8 97 2 0 50 4 7 120 27 6 700 20 5 520 3 9 100 2 4 61 1 3 34 10 2 258 7 5 190 4 3 110 1 1 27 7 0 177 4 2 106 6 4 162 1 4 35 5 9 150 1 3 33 5 1 1...

Страница 6: ...2 2 57 20 5 520 Mount the upper two nuts as shown in the figure below Tighten the lower two nuts after the unit has been mounted 0 04 to 0 08 1 to 2 0 6 15 MAX Screwdriver Knockout hole 5 9 150 15 7 400 10 8 275 Rear Anchor bolts two at left and right Front 2 3 7 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained A...

Страница 7: ...rvals of 8 2 to 9 10 2 5 to 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated Use the flare nut attached with the indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Unit in mm Connecting refrigerant piping Flaring 1 Cut th...

Страница 8: ...o gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements If incorrect incomplete wiring is...

Страница 9: ...p to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION Do not put the remote control wires and power supply wires AC208 230 V in the same conduit Doing so may cause trouble in the control system due to noise...

Страница 10: ...as per the Installation Manual supplied with the outdoor unit L2 L1 B A Indoor Outdoor control wire Remote control terminal block Power supply terminal block Electrical control box Ground screw Cord clamp Power supply wire Remote control wire Control wire between indoor and outdoor units L1 L2 0 8 20 1 2 30 0 4 10 Ground wire 0 08 2 or less Power supply wires and control wire A B A B Terminal bloc...

Страница 11: ...yed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be confirmed 3 Specify CODE No with TEMP buttons 4 Select SE...

Страница 12: ...ddress setup refer to the Installation Manual attached to the outdoor unit SET DATA 0000 0001 Remote control sensor Not used Factory default Used 9 How to change the discharge port The air discharging direction of the indoor unit has been set to forward direction as factory default However it is possible to change to upward direction Change the discharging direction according to conditions of the ...

Страница 13: ...eration stops by turning the thermostat OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices Wired remote control 1 Push button for 4 seconds or more TEST is displayed on the display part a...

Страница 14: ...y part of the remote control The error code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurs on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up to 4 errors The log can be...

Страница 15: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Страница 16: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Страница 17: ...refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No pa...

Страница 18: ...0H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANG...

Отзывы: