– 5 –

Fixing the indoor unit to wall

Fix the indoor unit to the wall as described below.

1

Fix four 0.3" (M8) anchor bolts to the wall, as 
shown in the following figure.

2

Attach the bolts carefully to the upper two 
anchor bolts, as shown in the following 
figure.

3

Open the knockout hole at rear side of the 
indoor unit with a screwdriver.

4

Hang the indoor unit to the anchor bolts.

5

Tighten the nuts to the two lower anchor 
bolts.

Unit: in (mm)

Fixing the indoor unit to floor

To fix the indoor unit to the floor, pass two anchor bolts
attached on the floor through a hole of the bottom plate 
of the indoor unit. Tighten and fix it with the nuts.

Unit: in (mm)

Installation of remote control 
(Sold separately)

For installation of the wired remote control, follow the 
Installation Manual attached with the remote control.
• Pull out the remote control cord together with the 

refrigerant pipe or drain pipe.
Pass the remote control cord through upper side of 
the refrigerant pipe and drain pipe.

• Do not leave the remote control at a place exposed 

to direct sunlight and near a stove.

Wireless remote control

The sensor of indoor unit with wireless remote control 
can receive a signal from a distance within approx. 23’ 
(7 m). Based on this, determine a place where the 
remote control can be operated and the installation 
place.
• Operate the remote control, confirm that the indoor 

unit receives a signal, and then install it.

• Keep it 3.3' (1 m) or more from devices such as 

television, stereo etc.
(Disturbance of image or noise may generate.)

• To prevent malfunction, select a place away from 

fluorescent light or direct sunlight.

• Two indoor units with wireless type remote control 

can be installed in the same room.

27.6" (700)

4.9" 

(125)

8.5" (215)

5.2"

(133)

17.3"

 (440)

2.2"

 (57)

20.5" (520)

Mount the upper two nuts as 

shown in the figure below.

Tighten the lower two nuts after 

the unit has been mounted.

0.04" to 0.08"

(1 to 2)

0.6" (15) MAX

Screwdriver

Knockout hole

5.9" 

(150)

15.7" (400)

10.8" (275)

Rear

Anchor bolts (two at left and right)

Front

23’

 (7

 m)

 or

 less

5

Drain piping

CAUTION

Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a 
heat insulation so as not to cause a dew condensation.
Inappropriate piping work may result in water leakage in the room and wet furniture.

After opening the knockout hole, deburr the edge.

Burrs adhered to opening of the knockout hole may causes an injury by touching it.

• Provide the indoor drain piping with proper heat insulation.
• Provide the area where the pipe connects to the indoor unit with proper heat insulation. Improper heat insulation 

will cause condensation to form.

• The drain pipe must be sloping downward (at an angle of 1/100 or more), and do not run the pipe up and down 

(arched shape) or allow it to form traps. Doing so may cause abnormal sounds.

• Restrict the length of the traversing drain pipe to 65.6’ (20 m) or less. For a long pipe, provide support brackets 

at intervals of 4’11" to 6’7" (1.5 to 2 m) to prevent flapping.

• Install the collective piping as shown in the following figure.
• Do not provide any air vents. Otherwise, the drain water will spout, causing water to leak.
• Do not allow any force to be applied to the connection area with the drain pipe.

Pipe material, size and insulator

The following materials for piping work and insulating process are procured locally.

Pipe material

Hard vinyl chloride pipe, pipe elbow (Nominal inner diameter Ø0.8" (20 mm))

Insulator

Foamed polyethylene foam, thickness: 0.4" (10mm) or more

Drain pan

Drain hose

Use adhesive for hard polyvinyl chloride pipe

Hard polyvinyl chloride pipe

Elbow

Insulation

9-EN

10-EN

+00EB99808701-1_01EN.book  Page 5  Thursday, June 23, 2016  11:57 AM

Содержание MML-AP0074H2UL

Страница 1: ...al use Pour usage commercial Indoor Unit Model name Floor Console Exposed Type MML AP0074H2UL MML AP0094H2UL MML AP0124H2UL MML AP0154H2UL MML AP0184H2UL MML AP0244H2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EB99808701 1_01EN book Page 1 Thursday June 23 2016 11 57 AM ...

Страница 2: ...ctric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes wa...

Страница 3: ...re the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner CAUTION This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Acco...

Страница 4: ...eyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adver...

Страница 5: ...oor installation Front panel screws Front panel Hock Hock Hock Hock Fan guard Air intake grille External dimensions Unit in mm 10 2 260 9 1 230 27 2 690 37 4 950 24 8 630 6 1 155 9 4 240 7 9 200 1 4 35 5 2 133 17 3 440 2 2 57 5 1 130 1 2 30 1 4 35 2 8 70 3 8 97 2 0 50 4 7 120 27 6 700 20 5 520 3 9 100 2 4 61 1 3 34 10 2 258 7 5 190 4 3 110 1 1 27 7 0 177 4 2 106 6 4 162 1 4 35 5 9 150 1 3 33 5 1 1...

Страница 6: ...2 2 57 20 5 520 Mount the upper two nuts as shown in the figure below Tighten the lower two nuts after the unit has been mounted 0 04 to 0 08 1 to 2 0 6 15 MAX Screwdriver Knockout hole 5 9 150 15 7 400 10 8 275 Rear Anchor bolts two at left and right Front 2 3 7 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained A...

Страница 7: ...rvals of 8 2 to 9 10 2 5 to 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated Use the flare nut attached with the indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Unit in mm Connecting refrigerant piping Flaring 1 Cut th...

Страница 8: ...o gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements If incorrect incomplete wiring is...

Страница 9: ...p to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION Do not put the remote control wires and power supply wires AC208 230 V in the same conduit Doing so may cause trouble in the control system due to noise...

Страница 10: ...as per the Installation Manual supplied with the outdoor unit L2 L1 B A Indoor Outdoor control wire Remote control terminal block Power supply terminal block Electrical control box Ground screw Cord clamp Power supply wire Remote control wire Control wire between indoor and outdoor units L1 L2 0 8 20 1 2 30 0 4 10 Ground wire 0 08 2 or less Power supply wires and control wire A B A B Terminal bloc...

Страница 11: ...yed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be confirmed 3 Specify CODE No with TEMP buttons 4 Select SE...

Страница 12: ...ddress setup refer to the Installation Manual attached to the outdoor unit SET DATA 0000 0001 Remote control sensor Not used Factory default Used 9 How to change the discharge port The air discharging direction of the indoor unit has been set to forward direction as factory default However it is possible to change to upward direction Change the discharging direction according to conditions of the ...

Страница 13: ...eration stops by turning the thermostat OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices Wired remote control 1 Push button for 4 seconds or more TEST is displayed on the display part a...

Страница 14: ...y part of the remote control The error code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurs on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up to 4 errors The log can be...

Страница 15: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Страница 16: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Страница 17: ...refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No pa...

Страница 18: ...0H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANG...

Отзывы: