Test run

Before test run

• Before turning on the power supply, carry out the 

following procedure.

1) By using 500 V-megger, check that resistance 

of 1 M

Ω

 or more exists between the terminal 

block L to N and the ground.
If resistance of less than 1 M

Ω

 is detected, do 

not run the unit.

2) Check the valve of the outdoor unit being 

opened fully.

• To protect the compressor at activation time, leave 

power-ON for 12 hours or more before operating.

• Do not press the electromagnetic contactor to 

forcibly perform a test run. (This is very dangerous in 
case the protective device does not work.)

• Before starting a test run, set addresses by following 

the Installation Manual supplied with the outdoor 
unit.

Execute a test run

• When a fan operation is to be performed for an 

individual indoor unit, turn off the power, short CN72 
on the circuit board, and then turn the power back 
on. (First set the operating mode to “fan,” and then 
operate.) When the test run has been performed 
using this method, do NOT forget to release the 
shorting of CN72 after the test run is completed.

Operate the unit with the wired remote control as usual.
For the procedure of the operation, refer to the 
attached to the outdoor unit Owner’s Manual.
A forced test run can be executed in the following 
procedure even if the operation stops by turning the 
thermostat - OFF.
In order to prevent a serial operation, the forced test 
run is released after 60 minutes have passed and 
returns to the usual operation.

CAUTION

Do not use the forced test run for cases other than the 
test run because it applies an excessive load to the 
devices.

Wired remote control

1

Push 

 button for 4 seconds or more. 

[TEST] is displayed on the display part and 
the selection of mode in the test mode is 
permitted.

2

Push  

button.

3

Select the operation mode with 

 

button, [

Cool] or [

Heat].

• Do not run the air conditioner in a mode other 

than [

Cool] or [

Heat].

• The temperature controlling function does not 

work during test run.

• The detection of error is performed as usual.

4

After the test run, push 

 button to 

stop a test run.

(Display part is same as procedure 1.)

5

Push 

 button to cancel (release from) the 

test run mode.

([TEST] disappears on the display and the status 
returns to a normal.)

2, 4
3

1,5

Wireless remote control

(TCB-AX32-UL)

1

When TEMPORARY button is pushed for 10 
seconds or more, “Pi!” sound is heard and 
the operation changes to a forced cooling 
operation. After approx. 3 minutes, a cooling 
operation starts forcedly.

Check cool air starts blowing. If the operation does 
not start, check wiring again.

2

To stop a test operation, push TEMPORARY 
button once again (Approx. 1 second).

• Check wiring / piping of the indoor and outdoor 

units in forced cooling operation.

TEMPORARY button

23-EN

24-EN

+00EB99808701-1_01EN.book  Page 12  Thursday, June 23, 2016  11:57 AM

Содержание MML-AP0074H2UL

Страница 1: ...al use Pour usage commercial Indoor Unit Model name Floor Console Exposed Type MML AP0074H2UL MML AP0094H2UL MML AP0124H2UL MML AP0154H2UL MML AP0184H2UL MML AP0244H2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EB99808701 1_01EN book Page 1 Thursday June 23 2016 11 57 AM ...

Страница 2: ...ctric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes wa...

Страница 3: ...re the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner CAUTION This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Acco...

Страница 4: ...eyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adver...

Страница 5: ...oor installation Front panel screws Front panel Hock Hock Hock Hock Fan guard Air intake grille External dimensions Unit in mm 10 2 260 9 1 230 27 2 690 37 4 950 24 8 630 6 1 155 9 4 240 7 9 200 1 4 35 5 2 133 17 3 440 2 2 57 5 1 130 1 2 30 1 4 35 2 8 70 3 8 97 2 0 50 4 7 120 27 6 700 20 5 520 3 9 100 2 4 61 1 3 34 10 2 258 7 5 190 4 3 110 1 1 27 7 0 177 4 2 106 6 4 162 1 4 35 5 9 150 1 3 33 5 1 1...

Страница 6: ...2 2 57 20 5 520 Mount the upper two nuts as shown in the figure below Tighten the lower two nuts after the unit has been mounted 0 04 to 0 08 1 to 2 0 6 15 MAX Screwdriver Knockout hole 5 9 150 15 7 400 10 8 275 Rear Anchor bolts two at left and right Front 2 3 7 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained A...

Страница 7: ...rvals of 8 2 to 9 10 2 5 to 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated Use the flare nut attached with the indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Unit in mm Connecting refrigerant piping Flaring 1 Cut th...

Страница 8: ...o gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements If incorrect incomplete wiring is...

Страница 9: ...p to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION Do not put the remote control wires and power supply wires AC208 230 V in the same conduit Doing so may cause trouble in the control system due to noise...

Страница 10: ...as per the Installation Manual supplied with the outdoor unit L2 L1 B A Indoor Outdoor control wire Remote control terminal block Power supply terminal block Electrical control box Ground screw Cord clamp Power supply wire Remote control wire Control wire between indoor and outdoor units L1 L2 0 8 20 1 2 30 0 4 10 Ground wire 0 08 2 or less Power supply wires and control wire A B A B Terminal bloc...

Страница 11: ...yed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be confirmed 3 Specify CODE No with TEMP buttons 4 Select SE...

Страница 12: ...ddress setup refer to the Installation Manual attached to the outdoor unit SET DATA 0000 0001 Remote control sensor Not used Factory default Used 9 How to change the discharge port The air discharging direction of the indoor unit has been set to forward direction as factory default However it is possible to change to upward direction Change the discharging direction according to conditions of the ...

Страница 13: ...eration stops by turning the thermostat OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices Wired remote control 1 Push button for 4 seconds or more TEST is displayed on the display part a...

Страница 14: ...y part of the remote control The error code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurs on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up to 4 errors The log can be...

Страница 15: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Страница 16: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Страница 17: ...refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No pa...

Страница 18: ...0H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANG...

Отзывы: