– 3 –

3

Selection of installation place

Avoid installing in the following places.

Select a location for the indoor unit where the cool or warm air will circulate evenly.
Avoid installation in the following locations.
• Saline area (coastal area).
• Locations with acidic or alkaline atmospheres (such as areas with hot springs, factories where chemicals or 

pharmaceuticals are made and places where the exhaust air from combustion appliances will be sucked into the 
unit). 
Doing so may cause the heat exchanger (its aluminum fins and copper pipes) and other parts to become 
corroded.

• Locations with atmospheres consisting of mist of cutting oil or other types of machine oil. 

Doing so may cause the heat exchanger to become corroded, mists caused by the blockage of the heat 
exchanger to be generated, the plastic parts to be damaged, the heat insulators to peel off, and other such 
problems to result.

• Locations where vapors from food oils are formed (such as kitchens where food oils are used). 

Blocked filters may cause the air conditioner’s performance to deteriorate, condensation to form, the plastic parts 
to be damaged, and other such problems to result.

• Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will 

be disrupted (a disruption of the air flow may cause the air conditioner’s performance to deteriorate or the unit to 
shut down).

• Locations where an in-house power generator is used for the power supply.

The power line frequency and voltage may fluctuate, and the air conditioner may not work properly as a result.

• On truck cranes, ships or other moving conveyances.
• The air conditioner must not be used for special applications (such as for storing food, plants, precision 

instruments or art works).
(The quality of the items stored may be degraded.)

• Locations where high frequencies are generated (by inverter equipment, in-house power generators, medical 

equipment or communication equipment).
(Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment’s operation.)

• Locations where there is anything under the unit installed that would be compromised by wetness.

(If the drain has become blocked or when the humidity is over 80%, condensation from the indoor unit will drip, 
possibly causing damage to anything underneath.)

• In the case of the wireless type of system, rooms with the inverter type of fluorescent lighting or locations 

exposed to direct sunlight.
(The signals from the wireless remote control may not be sensed.)

• Locations where organic solvents are being used.
• The air conditioner cannot be used for liquefied carbonic acid cooling or in chemical plants.
• Location near doors or windows where the air conditioner may come into contact with high-temperature, high-

humidity outdoor air.
(Condensation may occur as a result.)

• Locations where special sprays are used frequently.

Installation space

Unit: in (mm)

Reserve sufficient space required for installation or service work.

Filter cleaning sign term setting

The lighting term setup of the filter sign (Notification of filter cleaning) of the remote control can be changed 
according to the condition of installation.
For setup method, refer to “Filter sign setting” in the Applicable controls of this Manual.

11.8"

(300)

or more

19.7" (500) or more

39

.4

" (

100

0)

 

or

 mor

e

Front side

(In case of right direction piping)

Front side

5-EN

6-EN

+00EB99808701-1_01EN.book  Page 3  Thursday, June 23, 2016  11:57 AM

Содержание MML-AP0074H2UL

Страница 1: ...al use Pour usage commercial Indoor Unit Model name Floor Console Exposed Type MML AP0074H2UL MML AP0094H2UL MML AP0124H2UL MML AP0154H2UL MML AP0184H2UL MML AP0244H2UL AIR CONDITIONER MULTI TYPE Installation Manual 00EB99808701 1_01EN book Page 1 Thursday June 23 2016 11 57 AM ...

Страница 2: ...ctric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Connect ground wire grounding work Incomplete grounding may cause an electric shock Do not connect ground wires to gas pipes wa...

Страница 3: ...re the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner CAUTION This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Acco...

Страница 4: ...eyances The air conditioner must not be used for special applications such as for storing food plants precision instruments or art works The quality of the items stored may be degraded Locations where high frequencies are generated by inverter equipment in house power generators medical equipment or communication equipment Malfunctioning or control trouble in the air conditioner or noise may adver...

Страница 5: ...oor installation Front panel screws Front panel Hock Hock Hock Hock Fan guard Air intake grille External dimensions Unit in mm 10 2 260 9 1 230 27 2 690 37 4 950 24 8 630 6 1 155 9 4 240 7 9 200 1 4 35 5 2 133 17 3 440 2 2 57 5 1 130 1 2 30 1 4 35 2 8 70 3 8 97 2 0 50 4 7 120 27 6 700 20 5 520 3 9 100 2 4 61 1 3 34 10 2 258 7 5 190 4 3 110 1 1 27 7 0 177 4 2 106 6 4 162 1 4 35 5 9 150 1 3 33 5 1 1...

Страница 6: ...2 2 57 20 5 520 Mount the upper two nuts as shown in the figure below Tighten the lower two nuts after the unit has been mounted 0 04 to 0 08 1 to 2 0 6 15 MAX Screwdriver Knockout hole 5 9 150 15 7 400 10 8 275 Rear Anchor bolts two at left and right Front 2 3 7 m o r l e s s 5 Drain piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained A...

Страница 7: ...rvals of 8 2 to 9 10 2 5 to 3 m to clamp the refrigerant pipe Otherwise abnormal sound may be generated Use the flare nut attached with the indoor unit or R410A flare nut Permissible piping length and height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Unit in mm Connecting refrigerant piping Flaring 1 Cut th...

Страница 8: ...o gas pipes water pipes lightning rods or ground wires for telephone wires 3 Install appliance in accordance with national wiring regulations Capacity shortage of circuit breaker or incomplete installation may cause an electric shock or a fire CAUTION Consult local building codes NEC National Electrical Code or CEC Canadian Electrical Code for special requirements If incorrect incomplete wiring is...

Страница 9: ...p to 1312 4 400 m Total wire length of remote control inter unit wiring L1 L2 Ln Up to 656 2 200 m L1 L L2 Ln Indoor unit Remote control inter unit wiring Indoor unit Indoor unit Indoor unit Remote control Max 8 units Remote control wiring CAUTION Do not put the remote control wires and power supply wires AC208 230 V in the same conduit Doing so may cause trouble in the control system due to noise...

Страница 10: ...as per the Installation Manual supplied with the outdoor unit L2 L1 B A Indoor Outdoor control wire Remote control terminal block Power supply terminal block Electrical control box Ground screw Cord clamp Power supply wire Remote control wire Control wire between indoor and outdoor units L1 L2 0 8 20 1 2 30 0 4 10 Ground wire 0 08 2 or less Power supply wires and control wire A B A B Terminal bloc...

Страница 11: ...yed following ALL is the header unit 1 6 1 3 2 5 4 Display content varies with the indoor unit model 2 Each time button is pushed indoor unit numbers in the control group change cyclically Select the indoor unit to change settings for The fan of the selected unit runs and the louvers start swinging The indoor unit for change settings can be confirmed 3 Specify CODE No with TEMP buttons 4 Select SE...

Страница 12: ...ddress setup refer to the Installation Manual attached to the outdoor unit SET DATA 0000 0001 Remote control sensor Not used Factory default Used 9 How to change the discharge port The air discharging direction of the indoor unit has been set to forward direction as factory default However it is possible to change to upward direction Change the discharging direction according to conditions of the ...

Страница 13: ...eration stops by turning the thermostat OFF In order to prevent a serial operation the forced test run is released after 60 minutes have passed and returns to the usual operation CAUTION Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices Wired remote control 1 Push button for 4 seconds or more TEST is displayed on the display part a...

Страница 14: ...y part of the remote control The error code is only displayed during the operation If the display disappears operate the air conditioner according to the following Confirmation of error log for confirmation Confirmation of error log When an error occurs on the air conditioner the error log can be confirmed with the following procedure The error log is stored in memory up to 4 errors The log can be...

Страница 15: ...ted units Capacity over No of connected indoor units Combined capacity of indoor units exceeds 120 of combined capacity of outdoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during autom...

Страница 16: ...evice Wired remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp TD3 error I F P19 P19 Detected outdoor unit number ALT 4 ...

Страница 17: ...refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22 lbs 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 33 lbs 15 kg NOTE 2 The standards for minimum room volume are as follows 1 No pa...

Страница 18: ...0H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANG...

Отзывы: