102
Check code name
[P17] / [bb]
(Current code / AI-NET)
Check code name
Discharge temp TD2 error
Cause of operation
1. Outdoor unit service valve closed
2. Outdoor PMV error
3. TD sensor error
4. Refrigerant shortage, clogging of refrigerant
circuit
5. 4-way valve error
6. SV4 circuit leakage, misinstallation
Open service valves fully.
Repair outdoor PMV.
Replace TD2 sensor.
Check 4-way valve.
Correct cabling.
Are service valves of gas and
liquid sides fully opened?
Are characteristics of
TD2 sensor resistance normal?
Refrigerant shortage,
clogging, pipe breakage.
* Connectors CN300, 301 White
* Refer to outdoor unit
temperature sensor
characteristics-4.
(Check there is no pipe breakage, and then recharge refrigerant.)
Is outdoor PMV normal?
1. Connector connection
2. Cabling
3. Coil
4. Valve body
5. Outdoor I/F P.C. board
SV4 circuit
1. Are not SV41 and SV42 valve
coils installed reversely?
2. Is there no leakage through
SV42 circuit?
YES
NO
NO
YES
YES
YES
YES
NO
NO
NO
Is not an indoor unit of different
refrigerant line connected?
YES
NO
Correct installation of valve coil.
Replace SV42 valve.
Check with miscabling check
function of outdoor unit.
( )
Does not discharge
refrigerant gas bypass to suction side
through 4-way valve?
FILE NO. SVM-05052