106
Check code name
[P22] / [1A]
(Current code / AI-NET)
Check code name
Outdoor fan IPDU error
Cause of operation
1. Fan lock
2. Fan IPDU P.C. board error
3. Overload cause
4. External cause such as blast
5. Fan IPDU power P.C. board error
Sub-code:
0
∗
: IGBT short circuit
1
∗
: Position detect circuit error
3
∗
: Motor lock error
4
∗
: Motor current error detected
C
∗
: TH sensor error (Heat sink overheat)
D
∗
: TH sensor error
E
∗
: Vdc error
Is not outdoor fan motor locked?
Is sub-code of outdoor I/F P.C. board [0d]?
Check fan IPDU.
Correct cable connector connection.
Correct cause of overload.
Retightening of screws, etc.
Replace fan IPDU.
Is there no problem
such as stuffing or blast blowing to
discharge port of outdoor fan?
Are cable connector
connection on fan IPDU and
power P.C. board A’ssy normal?
Is there no loosening on fixation
between fan IPDU and heat sink?
Replace motor.
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
FILE NO. SVM-05052