Part name
Checking procedure
AP0096
BHPUL
AP0126
BHPUL
Measure the resistance value of each winding by using the tester.
1
2
3
4
5
Red
White
Black
Fan motor inside wiring diagram
ICF-340W150-1
A
, 2
A
Under 20 ˚C
Position
Black–Red
Black–White
Red–White
Resistance value
14.8 ± 1.5
Ω
14.8 ± 1.5
Ω
14.8 ± 1.5
Ω
ICF-340W250-1
A
Position
Black–Red
Black–White
Red–White
Resistance value
12.4 ± 1.2
Ω
12.4 ± 1.2
Ω
12.4 ± 1.2
Ω
ICF-340W150-1
A
MMD-AP0
15
6
BHPUL
AP0
18
6
BHPUL
Concealed Duct type
Fan motor
ICF-340W150-
2
A
MMD-AP0
0
7
6BHP
UL
- 81 -
ICF-340W
250
-1
A
MMD
-AP0216BHPUL
AP0
24
6
BHPUL
AP0
30
6
BHPUL
AP0
36
6
BHPUL
AP0426BHPUL
AP0486BHPUL
AP0546BHPUL
Содержание MMD-AP0076BHPUL
Страница 19: ...4 WIRING DIAGRAMS 19 Concealed Duct Type Wiring Diagram ...
Страница 95: ...MMD AP0156BHPUL MMD AP0186BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 95 ...
Страница 99: ...MMD AP0426BHPUL MMD AP0486BHPUL MMD AP0546BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 99 ...
Страница 102: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...