NO.
Item
Specification outline
Remarks
6
7
Cold air
discharge
prevention
control
1. In heating operation, the upper limit of the fan tap is set according to the
lower of whichever is the higher between TC2 sensor and TCJ sensor
temperatures, on the one hand, and TC1 sensor temperature, on the
other.
• If the fan continuously operates in zone B for 6 minutes, it automatically
moves into zone C.
• During defrosting, the control point is shifted by +6 °C.
TCJ: Indoor heat
exchanger
sensor
temperature
• In zones D and E,
priority is given
to the remote
controller fan
speed setting.
• In zone A,
“HEATING
STANDBY
”
is displayed.
Freeze
prevention
control (low
temp. release)
1. During cooling, the air conditioner is operated in the manner described
below according to the temperature readings of the TC1, TC2 and TCJ
sensors.
• If zone J operation is detected for 5 minutes, the air conditioner is forced
into thermo OFF.
• In zone K, the timer is put on pause, with the current timer count
retained.
• If zone I operation is detected, the timer count is cleared, and the air
conditioner returns to normal operation.
• If continuous zone J operation forces the air conditioner into thermo OFF,
the indoor fan is operated in breeze mode until it moves into zone I.
The control is terminated under the following conditions:
Termination conditions
TC1:
Indoor heat
exchanger
sensor
temperature
* With models
without TC2,
TC2 is not
part of the
control
parameters.
2. During cooling, the air conditioner is operated in the manner described
below according to the temperature readings of the TC2 and TCJ sensors.
• If zone M operation is detected for 45 minutes, the air conditioner is
forced into thermo OFF.
• In zone N, the timer is put on pause, with the current timer count
retained.
• When the air conditioner goes back into zone M, timer count is resumed
from the retained value.
• If zone L operation is detected, the timer count is cleared, and the air
conditioner returns to normal operation.
Reset conditions
E
B
A
A zone: OFF
B zone:
Over
78.8°F(
26°C
)
, below
82.4°F(
28°C
)
, ULTRA LOW (LL)
C zone:
Over
82.4°F(
28°C
)
, below
86°F(
30°C
)
, LOW (L)
D zone:
Over
86°F(
30°C
)
, below
89.6°F(
32°C
)
, MED (H)
E zone: HIGH (HH)
D
C
32
30
28
26
20
16
(°C)
89.6
86
82.4
78.8
68
33.8
(°
F
)
P1
Q1
(°C)
a
K
J
P1
Q1
TC1
32
°
F
(
0
°C)
TC2, TCJ
14
°
F(-10°C)
6.8°F(-14°C)
(°
F
)
50
°
F
(
10
°C)
(41°F)(5°C)
P2
Q2
(°C)
L
N
M
P2
Q2
TC2, TCJ
41°F(
5°C
)
28.4
°
F(–2.0°C)
1)
TC1
Ӎ
53.6°F(
12°C
)
and TC2
Ӎ
53.6°F(
12°C
)
and
TCJ
Ӎ
53.6°F(
12°C
)
2)
20 minutes passed after stop.
1)
TC1
Ӎ
53.6°F(
12°C
)
and TC2
Ӎ
53.6°F(
12°C
)
and
TCJ
Ӎ
53.6°F(
12°C
)
2)
20 minutes passed after stop.
- 24 -
Содержание MMD-AP0076BHPUL
Страница 19: ...4 WIRING DIAGRAMS 19 Concealed Duct Type Wiring Diagram ...
Страница 95: ...MMD AP0156BHPUL MMD AP0186BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 95 ...
Страница 99: ...MMD AP0426BHPUL MMD AP0486BHPUL MMD AP0546BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 99 ...
Страница 102: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...