Check code
Display of receiving unit
Typical fault site
Description of error
Outdoor 7-segment display
Indicator light block
Sub-code
Flash
Timer Ready
Operation
⎯
⎯
⎯
⎯
⎯
⎯
E01
E02
E02
Main
remote
controller
No master remote controller,
faulty remote controller
communication (reception)
Faulty remote controller
communication (transmission)
Signals cannot be received from indoor unit; master remote
controller has not been set (including two remote controller
control).
Signals cannot be transmitted to indoor unit.
Duplicated master remote
controller
Both remote controllers have been set as master remote
controller in two remote controller control (alarm and
shutdown for header unit and continued operation for
follower unit)
(Error detected by main remote controller)
Check code
Display of receiving unit
Typical fault site
Description of error
Outdoor 7-segment display
Indicator light block
Sub-code
Flash
Timer Ready
Operation
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
C05
⎯
⎯
C06
C12
P30
(Error detected by central control device)
TCC-LINK
central
control
No indication
(when main remote
controller also in
use)
Faulty central control
communication (transmission)
Faulty central control
communication (reception)
Multiple network adapters
Central control device is unable to transmit signal due to
duplication of central control device (AI-NET).
Central control device is unable to receive signal.
Multiple network adapters are connected to remote
controller communication line (AI-NET).
Blanket alarm for general-
purpose device control
interface
Device connected to general-purpose device control
interface for TCC-LINK / AI-NET is faulty.
As per alarm unit (see
above)
Group control follower unit
error
Group follower unit is faulty (unit No. and above detail
[
∗∗∗
] displayed on main remote controller)
Note:
The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it.
Moreover, check codes detected by the main remote controller / central control device do not necessarily have a direct impact on air
conditioner operation.
- 53 -
Содержание MMD-AP0076BHPUL
Страница 19: ...4 WIRING DIAGRAMS 19 Concealed Duct Type Wiring Diagram ...
Страница 95: ...MMD AP0156BHPUL MMD AP0186BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 95 ...
Страница 99: ...MMD AP0426BHPUL MMD AP0486BHPUL MMD AP0546BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 99 ...
Страница 102: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...