0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
300
500
700
900
1100
1300
1500
1700
1900
2100
Air flow rate (CFM)
AP0366, AP0426 type
Standard air flow: 1130 CFM
Standard filter pressure loss
Mid tap
0.6 in.WG-
igh
0.8 in.WG- H
0.8
High tap
0.6 in.WG-
High tap
0.4 in.WG-
0.12 in.WG- High tap
0.6 in.WG- Low tap
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
300
500
700
900
1100
1300
1500
1700
1900
2100
External static pressure(in.WG)
Air flow rate (CFM)
AP0486, AP0546 type
Standard air flow: 1177 CFM
Standard filter pressure loss
High tap
0.8 in.WG-
0.6 in.WG- High tap
0.4 in.WG- High tap
in.WG- High tap
0.12
0.6 in.WG- Mid tap
0.6 in.WG- Low tap
External static pressure(in.WG)
- 16 -
The concealed duct unit has 7 steps of static pressure (MMD-AP0076 ~ 0186BHPUL is 0.12 – 0.6 in. WG,
MMD-AP0216 ~ 0546BMPUL is 0.12 – 0.8 in. WG) adjustment to meet the installation site requirements /
conditions.
With these steps there are different speed fan taps associated to select correct air fl ow.
For meeting the site requirement / conditions, make sure the external static pressure and air fl ow are determined.
Plot the external static pressure and air fl ow on the below graph to determine the right speed fan step setting.
For example : Job site requirement is to deliver 400 CFM at 0.4 in. WG external static pressure. Using the below
graph, external static pressure on vertical axis and air fl ow on horizontal axis, the star mark indicates the job site
requirement.
The star mark is below 0.6 in. WG high speed fan tap line, which means the unit needs to be set to 0.6 in WG
external static pressure with high speed fan tap.
Please follow the process described in application controls of this manual for set up external static pressure.
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0
100
200
300
400
500
600
700
Air flow rate (CFM)
AP0076 type
Standard air flow: 318 CFM
0.6 in.WG- High tap
0.4 in.WG- High tap
0.26 in.WG- High tap
0.4 in.WG- Low tap
0.4 in.WG- Mid tap
Standard filter pressure loss
0.12 in.WG- High tap
External static pressure(in.WG)
★
NOTE
Supply air CFM will follow the solid line fan curve shown in the above graph if there is any change in the external
static pressure.
Supply air volume for medium and low fan speed tap is also set by remote controller. It will follow the dotted line
fan curve in the graph.
Содержание MMD-AP0076BHPUL
Страница 19: ...4 WIRING DIAGRAMS 19 Concealed Duct Type Wiring Diagram ...
Страница 95: ...MMD AP0156BHPUL MMD AP0186BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 95 ...
Страница 99: ...MMD AP0426BHPUL MMD AP0486BHPUL MMD AP0546BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 99 ...
Страница 102: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...