NO.
Item
Specification outline
Remarks
14
Filter sign
display
(not applicable
to wireless type)
*Provided in
the separately
mounted type,
TCB-AX21E.
1. The indoor fan’s cumulative hours of operation are counted, and when
these exceed the prescribed value (2500H), a filter replacement signal
is sent to the remote controller to display a filter sign on it.
2. When a filter reset signal is received from the remote controller, the
timer measuring cumulative hours is cleared. If the prescribed hours
have been exceeded, the hours count is reset, with the sign on the
remote controller display erased.
“FILTER ” displayed
2500H
Filter service life
Operation
standby
Heating standby
15
<Operation standby> .......... Displayed on remote controller
1. When any of the DN codes listed below is displayed
• “P05” - Detection of an open phase in the power supply wiring
• “P10” - Detection of indoor flooding in at least one indoor unit
• “L30” - Detection of an interlock alarm in at least one indoor unit
2. Forced thermo OFF
• “COOL / DRY” operation is unavailable because at least one indoor
unit is operating in “HEAT” mode.
• “HEAT” operation is unavailable because at least one indoor unit is
operating in
“COOL / DRY” mode under priority cooling setting (bit 1 of SW11 on
outdoor I/ F P.C. board ON).
3. All indoor units not able to engage in any of the above operations
stand by in thermo OFF state.
4. The indoor fan has been turned off because the system is engaged in
a heat refrigerant (oil) recovery operation.
<Heating standby> .......... Displayed on remote controller
1. Normal thermo OFF
• During heating, the indoor unit goes thermo OFF as the heating
temperature setting is reached.
2. During heating, the fan rotates at a breeze speed (UL or lower) or
remains stationary to prevent cold air from being discharged
(including defrosting operation).
3.Forced thermo OFF
• “HEAT” operation is unavailable because at least one indoor unit is
operating in
“COOL / DRY” mode under priority cooling setting (bit 1 of SW11 on
outdoor I/ F P.C. board ON).
• “OPERATION
STANDBY
”
displayed
No display
provided on
wireless remote
controller
16
Selection of
central control
mode
1. The range of operations that can be performed via an indoor unit
remote controller can be determined through the setting of the central
controller.
2. Setting details
• In the case of a
wired remote
controller,
“CENTRAL
CONTROL IN
PROGRESS
”
is displayed (lit up)
while in central
control mode.
• The display blinks
when a control
function
inaccessible to a
remote controller is
chosen.
• A wireless remote
controller has the
same set of control
functions, although
there is no display.
When a control
operation is
performed via a
wireless remote
controller while in
central control
mode, a peep
sound alert (5
times) is provided.
TCC-Link central control
(
{
: Accessible
×
: Inaccessible)
Operation on RBC-AMT32
UL
Operation
via TCCLink
central
control
RBC-
AMT32UL
display
“
CENTRAL
CONTROL
IN
PROGRESS
”
Start / stop
selection
Operation
mode
selection
Timer
setting
Temperature
setting
Fan speed
setting
Air flow
direction
setting
Individual
Central 1
Central 2
Central 3
Central 4
{
×
×
{
{
{
{
×
×
×
{
×
×
{
{
{
{
×
×
{
{
{
{
{
{
{
{
{
{
{
• “HEATING
STANDBY
”
displayed
- 26 -
Содержание MMD-AP0076BHPUL
Страница 19: ...4 WIRING DIAGRAMS 19 Concealed Duct Type Wiring Diagram ...
Страница 95: ...MMD AP0156BHPUL MMD AP0186BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 95 ...
Страница 99: ...MMD AP0426BHPUL MMD AP0486BHPUL MMD AP0546BHPUL 238 2 241 233 235 244 242 243 213 203 ACCESSORY PARTS 99 ...
Страница 102: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...