Equivalent HP
Equivalent to 8HP
Equivalent to 10HP
Model name
Heat Pump
MMY-
MP0801HT7
MP1001HT7
Outdoor unit type
Inverter unit
Inverter unit
Cooling capacity (
*
1)
(kW)
22.4
28.0
Standard heating capacity (
*
1)
(kW)
25.0
31.5
Power supply (
*
2)
3 phase 60Hz 380V
Running current
(A)
17.9
21.4
Power consumption
(kW)
11.2
13.4
Power factor
(%)
90
90
EER (Energy Efficiency Ratio)
(kW/kW)
2.00
2.09
Starting current
(A)
15.5
18.2
Cooling
Instantaneous maximum current
(A)
92
93
Running current
(A)
17.2
21.1
Power consumption
(kW)
10.8
13.2
Power factor
(%)
91
90
EER (Energy Efficiency Ratio)
(kW/kW)
2.31
2.39
Starting current
(A)
14.7
18.0
Electrical
characteristics
(
*
1)
Heating
Instantaneous maximum current
(A)
92
93
External dimension
(mm)
Height 1,700 x Width 990 x Depth 750
Total weight
(kg)
265
270
Color
Silky shade (Munsell 1Y8.5/0.5)
Type
Hermetic type
Compressor
Motor output
(kW)
6.0
7.5
Fan
Propeller fan
Motor output
(kW)
0.35
Fan unit
Air volume
(m³/h)
10,000
Heat exchanger
Finned tube
Refrigerant R407C (Charged refrigerant amount) (
*
3)
(kg)
R407C (15.5)
R407C (17.0)
Inverter drive side
(MPa)
OFF : 3.2 ON : 2.55
High-pressure switch
Fixed-speed side
(MPa)
OFF : 2.55 ON : 3.2
Protective devices
Discharge temp. sensor, Suction temp. sensor, Inner overload relay,
Compressor over-current relay, Over-current sensor, Low-pressure sensor
Case heater
(W)
——
——
Gas side
(mm)
Ø25.4
Ø28.6
Liquid side
(mm)
Ø12.7
Ø12.7
Connecting
port dia
Balance pipe
(mm)
Ø9.5
Ø9.5
Gas side
Brazing
Brazing
Liquid side
Flare
Flare
Connecting
method
Balance pipe
Flare
Flare
Max. equivalent length
(m)
125
Max. real length
(m)
100 (However, if equivalent bend length is longer, equivalent length is the
standard.)
Max. total pipe length (Real length)
(m)
250
Outdoor unit is higher than indoor unit : 50
Refrigerant
piping
specifications
(
*
4)
Max. height difference
(m)
Outdoor unit is lower than indoor unit : 30
Central wiring
Shield wire 1.25mm² x 2 cores. up to 500m
Central remote controller
MVVS (Shield wire) 1.25mm² x 2 pcs. up to 500m
MVVS (Shield wire) 2.0mm² x 2 pcs. up to 1000m
Max. No. of connected indoor units
13
16
Sound level
(dB•A)
57
Outdoor unit (60Hz)
60Hz
*
1 : Rated conditions
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
The standard piping measns that main pipe length is 3 m, branching pipe length 2 m of branch piping connected with a 0
meter height.
*
2 : The source voltage must not fluctuate more than ±10%.
*
3 : The amount does not consider extra piping lengths. Refrigerant must be added on site in accordance with the actual piping length.
*
4 : The maximum total piping length indicates the sum of one-way piping lengths on the liquid side or gas side.