![Toshiba MMC-P0151H Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/toshiba/mmc-p0151h/mmc-p0151h_design-manual_423774038.webp)
1-36
Model name
MMD-
P 0 0 7 1 B H
P 0 0 9 1 B H
P 0 1 2 1 B H
P 0 1 5 1 B H
P 0 1 8 1 B H
P 0 2 4 1 B H
P 0 3 0 1 B H
P 0 3 6 1 B H
P 0 4 8 1 B H
Cooling/Heating capacity (Note 1)
(kW)
2.2/2.5
2.8/3.2
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
9.0/10.0
11.2/12.5 14.0/16.0
Power supply
1 phase 50Hz 230V (220 — 240V) (Power exclusive for indoor is required.)
Running current
(A)
0.41
0.67
0.70
0.85
1.26
Power consumption
(kW)
0.087
0.143
0.145
0.179
0.267
Power factor
(%)
92
93
90
92
92
Electrical
characteristics
Starting current
(A)
0.6
0.8
1.1
1.2
2.0
Appearance
Main unit
Zinc hot dipping steel plate
Height
(mm)
320
Width
(mm)
550
700
1,000
1,350
Main
unit
Depth
(mm)
800 (+75)
800 (+75)
800 (+75)
800 (+75)
Height
(mm)
5
Width
(mm)
630
780
1,080
1,430
Outer
dimension
Ceiling
panel
Depth
(mm)
500
Main unit
(kg)
38
43
57
74
Total weight
Ceiling panel
(kg)
3.5
4
6
7
Heat exchanger
Finned tube
Soundproof/Heat-insulating material
Non-flammable insulation
Fan
Centrifugal fan
Standard air flow High
(Mid./Low)
(m³/h)
480
(420/340)
570
(490/400)
840
(740/645)
1,140
(1,050/950)
1,320
(1,230/1,150)
1,680
(1,420/1,210)
2,040
(1,770/1,550)
Motor
(W)
60
100
120
140
External static pressure
(factory setting)
(Pa)
39.2 (4 mmAq)
Fan
unit
External static pressure
(Pa)
98 (10 mmAq)
Air filter
Field supply
Controller
Remote controller
Gas side
(mm)
Ø12.7
Ø15.9
Ø19.0
Liquid side
(mm)
Ø6.4
Ø9.5
Connecting
pipe
Drain port
(Nominal dia.)
25 (Polyvinyl chloride tube)
Sound level (Note 2)
(High/Mid./Low)
(dB•A
)
40
(37/34)
42
(39/36)
43
(40/37)
45
(42/39)
46
(43/40)
• Concealed Duct Type
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based on the
reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note
: Rated conditions
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
50Hz