1-27
n
Single outdoor unit
60Hz
NOTE : A fixed-speed unit cannot be used for a single outdoor unit. It is necessarily used together with an inverter unit.
n
Combination of outdoor unit
Legend
MCA : Minimum Circuit Amps
MOCP : Maximum Overcurrent Protection (Amps)
ICF
: Maximum Instantaneous Current Flow Start
RLA
: Rated Load Amps
LRA
: Locked Rotor Amps
FLA
: Full Load Amps
kW
: Fan Motor Rated Output (kW)
NOTE :
RLA is based on the following conditions.
Indoor temperature : 27°C DB/19°C WB
Outdoor temperature
: 35°C DB
Cooling only
Model MMY-
MP0801T7
MP1001T7
MP06017
MP08017
MP10017
Heat Pump Model
MMY-
MP0801HT7
MP1001HT7
MP0601H7
MP0801H7
MP1001H7
Nominal Voltage
(V-Ph-Hz)
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
Voltage Range
Min
Max
342
418
342
418
342
418
342
418
342
418
Compressor
RLA
LRA
11.5+11.5
77
13.1+13.1
77
13.1
77
11.5+11.5
77
13.1+13.1
77
Fan Motor
kW
FLA
0.35
3.2
0.35
3.2
0.35
3.2
0.35
3.2
0.35
3.2
Power Supply
MCA
MOCP
ICF
28.7
35
92
32.3
40
93
19.2
30
80
28.7
35
92
32.3
40
93
Type
Inv. unit
Fixed-speed unit
Cooling
only Model
MMY-
P1401T7
P1601T7
P1801T7
P2001T7
P2201T7
P2401T7
P2601T7
P2801T7
P3001T7
P3201T7
P3401T7
P3601T7
P3801T7
P4001T7
P4201T7
P4401T7
P4601T7
Heat Pump
Model
MMY-
P1401HT7
P1601HT7
P1801HT7
P2001HT7
P2201HT7
P2401HT7
P2601HT7
P2801HT7
P3001HT7
P3201HT7
P3401HT7
P3601HT7
P3801HT7
P4001HT7
P4201HT7
P4401HT7
P4601HT7
Nominal
Voltage
(V-Ph-Hz)
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
380-3-60
Voltage Range
Min
Max
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
342
418
Compressor
No.1
RLA
LRA
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
13.1+13.1 77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
13.1+13.1 77
13.1+13.1 77
11.5+11.5 77
13.1+13.1 77
13.1+13.1 77
13.1+13.1 77
13.1+13.1 77
13.1+13.1 77
13.1+10.1 77
13.1+13.1 77
No.2
RLA
LRA
13.1
77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
11.5+11.5 77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
13.1+13.1 77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
13.1+13.1 77
13.1+13.1 77
11.5+11.5 77
13.1+13.1 77
13.1+13.1 77
No.3
RLA
LRA
—
—
—
—
—
—
—
—
13.1
77
11.5+11.5 77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
11.5+11.5 77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
13.1+13.1 77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
No.4
RLA
LRA
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
11.5+11.5 77
11.5+11.5 77
11.5+11.5 77
11.5+11.5 77
13.1+13.1 77
11.5+11.5 77
11.5+11.5 77
11.5+11.5 77
No.5
RLA
LRA
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
11.5+11.5
77
11.5+11.5
77
11.5+11.5
77
Fan Motor
kW
FLA
0.35×2
6.4
0.35×2
6.4
0.35×2
6.4
0.35×2
6.4
0.35×3
9.6
0.35×3
9.6
0.35×3
9.6
0.35×3
9.6
0.35×3
9.6
0.35×4
12.8
0.35×4
12.8
0.35×4
12.8
0.35×4
12.8
0.35×4
12.8
0.35×5
16.0
0.35×5
16.0
0.35×5
16.0
Power Supply
MCA MOCP
ICF
45.8
60
106
55.3
70
118
58.9
70
120
62.1
80
123
72.0
90
133
81.5
100
144
85.1
100
146
87.3
110
148
91.5
110
152
107.7
130
170
111.3
130
172
114.5
150
175
117.7
150
178
120.9
150
182
137.5
170
198
140.7
170
201
143.9
170
205