1-3
Inverter unit
Fixed-speed unit
Appearance
Corresponding HP
8 HP
10 HP
6 HP
8 HP
10 HP
Cooling only MMY-
MP0801T8
MP1001T8
MP06018
MP08018
MP10018
Heat pump
MMY- M P 0 801H T8
M P 1 00 1 H T 8
MP0601H8 MP0801H8 MP1001H8
Model
name
Heat pump
MMY- M P 0 801H T7
M P 1 00 1 H T 7
MP0601H7 MP0801H7 MP1001H7
Cooling capacity (kW)
22.4
28.0
16.0
22.4
28.0
Heating capacity (kW)
25.0
31.5
18.0
28.0
31.5
Model name
Usage
Appearance
RBM-BY52E
Indoor unit capacity code (*1) : Total below 6.4
RBM-BY102E
Indoor unit capacity code (*1) : Total 6.4 or more and below 13.2
(*2)
RBM-BY202E
Indoor unit capacity code (*1) : Total 13.2 or more and below 25.2
(*2)
Y-shape branching
joint (*3)
RBM-BY302E
Indoor unit capacity code (*1) : Total 25.2 or more
(*2)
RBM-HY1042E Indoor unit capacity code (*1) : Total below 13.2
4-branching header
(*4)
RBM-HY2042E Indoor unit capacity code (*1) : Total 13.2 or more and below 25.2
Max.4
branches
RBM-HY1082E Indoor unit capacity code (*1) : Total below 13.2
8-branching header
(*4) (*5)
RBM-HY2082E Indoor unit capacity code (*1) : Total 13.2 or more and below 25.2
Max.8
branches
1 set of 3 types of T-shape joint pipes as described below:
The required quantity is arranged and they are combined at the site.
Connection piping
Corresponded dia. (mm)
Q'ty
Balance pipe
Ø9.52
1
Piping at liquid side
Ø12.7 to Ø25.4
1
Piping at gas side
Ø25.4 to Ø50.8
1
T-shape branching
joint
(For connection of
outdoor units)
RBM-BT12E
1-2. SUMMARY OF SYSTEM COMPONENTS
Components
1. Outdoor units
*
1 “Capacity code” can be obtained from page 1-12. (Capacity code is not actual capacity)
*
2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.
*
3 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.
*
4 Max. 6.0 capacity code in total can be connected.
*
5 If capacity code of outdoor unit is 26 and more, it is not used for 1st branching.
*
6 Model names for outdoor and indoor units described in this guide are shortened because of the space constraint.
2. Outdoor units (Combination of outdoor units)
3. Branching joints and headers
Corresponding HP
8 HP
10 HP
14 HP
16 HP
18 HP
20 HP
22 HP
24 HP
26 HP
28 HP
MMY- MP0801T8
MP1001T8
P1401T8
P1601T8
P1801T8
P2001T8
P2201T8
P2401T8
P2601T8
P2801T8
MMY- MP0801HT8 MP1001HT8
P1401HT8
P1601HT8
P1801HT8
P2001HT8
P2201HT8
P2401HT8
P2601HT8
P2801HT8
Combined
Model
MMY- MP0801HT7 MP1001HT7
P1401HT7
P1601HT7
P1801HT7
P2001HT7
P2201HT7
P2401HT7
P2601HT7
P2801HT7
Cooling capacity (kW)
22.4
28.0
38.4
45.0
50.4
56.0
63.0
69.0
73.0
80.0
Heating capacity (kW)
25.0
31.5
43.0
53.0
59.5
63.0
71.0
81.0
87.5
91.0
Inverter unit
8 HP
10 HP
8 HP
8 HP
10 HP
10 HP
8 HP
8 HP
10 HP
10 HP
—
—
6 HP
8 HP
8 HP
10 HP
8 HP
8 HP
8 HP
10 HP
—
—
—
—
—
—
6 HP
8 HP
8 HP
8 HP
—
—
—
—
—
—
—
—
—
—
Combined
outdoor
units
Fixed-
speed unit
—
—
—
—
—
—
—
—
—
—
No. of connectable
indoor units
13
16
16
18
18
20
22
24
26
28
Corresponding HP
30 HP
32 HP
34 HP
36 HP
38 HP
40 HP
42 HP
44 HP
46 HP
MMY-
P3001T8
P3201T8
P3401T8
P3601T8
P3801T8
P4001T8
P4201T8
P4401T8
P4601T8
MMY- P3001HT8
P3201HT8
P3401HT8
P3601HT8
P3801HT8
P4001HT8
P4201HT8
P4401HT8
P4601HT8
Combined
Model
MMY- P3001HT7
P3201HT7
P3401HT7
P3601HT7
P3801HT7
P4001HT7
P4201HT7
P4401HT7
P4601HT7
Cooling capacity (kW)
85.0
90.0
95.2
102.4
106.4
112.0
117.6
123.2
128.8
Heating capacity (kW)
94.5
109.0
115.5
119.0
122.5
126.0
143.5
147.0
150.5
Inverter unit
10 HP
8 HP
10 HP
10 HP
10 HP
10 HP
10 HP
10 HP
10 HP
10 HP
8 HP
8 HP
10 HP
10 HP
10 HP
8 HP
10 HP
10 HP
10 HP
8 HP
8 HP
8 HP
10 HP
10 HP
8 HP
8 HP
10 HP
—
8 HP
8 HP
8 HP
8 HP
10 HP
8 HP
8 HP
8 HP
Combined
outdoor
units
Fixed-
speed unit
—
—
—
—
—
—
8 HP
8 HP
8 HP
No. of connectable
indoor units
30
32
34
36
38
40
40
40
40