– 5 –
Installation Manual
EN-9
EN-10
CAUTION
1. Install the outdoor unit in a location where the discharge air is not blocked.
2. When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high
stories of a building, secure normal fan operation by using a duct or wind shield.
3. When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper stairs
or rooftop of a building, apply the wind-proofing measures referred to in the following examples.
1) Install the unit so that its discharge port faces the wall of the building.
Keep a distance 500 mm or more between the unit and wall surface.
2) Leave a clearance of at least 250 mm between the right side panel and wall or other surface of the building for
installation and servicing purposes.
250 mm
3) Leave a clearance of at least 200 mm between the rear panel and wall or other surface of the building in order to
maintain the performance of the air conditioner.
4) Consider the wind direction during the operational season of the air conditioner, and install the unit so that the
discharge port is set at a right angle relative to the wind direction.
2FAN_IM_DB04905901-00.book Page 5 Friday, October 24, 2014 3:19 PM
Strong wind
Strong wind
2
00 mm
500 mm