Allowable length / height difference of refrigerant piping
*1 Furthest indoor unit from 1st branch to be named “A”.
Allowable
value
Pipes
Piping Length
Total extension of pipe (liquid pipe, real length)
9
0 m
L1 + L2 + L3 + a + b + c + d + e
+ f
Furthest piping length L
(*1)
Real length
5
0 m
L1 + L3 +
f
Equivalent length
6
0 m
Max. equivalent length of main pipe
3
0 m
L1
Max. real length of furthest piping from 1st
branching Li (*1)
20 m
L3 +
f
Max. real length of indoor unit connecting pipe
10 m
a, b, c, d, e
, f
Height
Difference
Height between indoor
and outdoor units H1
Upper outdoor unit
15 m
Lower outdoor unit
15 m
Height between indoor units H2
10 m
Outdoor unit
2FAN_IM_DB04905901-00.book Page 11 Friday, October 24, 2014 3:19 PM
L2
L1
d
L3
e
f
Y-shaped
branching joint
Main pipe
1st branching
pipe
section
Branching
Branching
header
Indoor unit
pipe
Branching
Heigh
ce
between indoor and
outdoor units H1
Height
erence
units H2
between indoor
Equivalent length corresponded to farthest piping after 1st branching Li
a
b
c
Equivalent length corresponded to farthest piping L
A
*1
Outdoor unit
L
Main pipe
Indoor unit
Hight difference
between indoor and
outdoor unit H
In case of 2 to 6 indoor units connecting.
In case of 1 indoor units connecting.
Real length of main pipe
Hight difference between indoor and
outdoor unit
Upper outdoor unit
Allowable
7.5 m - 50 m
Lower outdoor unit
Pipes
15 m
15 m
L
H