– 25 –

Installation Manual

To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)

(When communication wirings of 2 or more refrigerant lines are interconnected for central control)

NOTE

You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.

* Enter the address check / change mode and change the addresses.

If no number appears on UNIT No., no outdoor unit exists on the line. Push 

 

button and select another line following 

step 2.

(Execute it while the units are stopped.)

1

Push and hold the TIME 

 and 

 buttons at the same time for more than 4 seconds. 

At first, the line 1 and CODE No. 

 

(Address Change) are indicated on the LCD display.

2

Push 

 (left side of the button) and 

 buttons repeatedly to select a system address.

3

Push the 

 

button.

• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display 

and the fan and louvers of the unit are activated.
At first, the current indoor unit address is displayed in SET DATA.
(No system address is indicated.)

3

1

2

ON / OFF

TEMP.

TIME

SET CL

FILTER

RESET TEST

TIMER SET

CODE No.

UNIT   No.

SETTING

DATA

SET

R.C.

No.

Cancels the line selection

UNIT  LOUVER

SWING/FIX

4

8

5, 7 

6

ON / OFF

TEMP.

TIME

SET CL

FILTER

RESET TEST

TIMER SET

CODE No.

UNIT   No.

SETTING

DATA

SET

R.C.

No.

Finish

Press to finish 
setting.

4

Push the TIME 

 / 

 buttons repeatedly to change the value of the indoor unit address in SET DATA. 

Change the value in SET DATA to that of a new address.

5

Push the 

 button to confirm the new address on SET DATA.

6

Push the 

 button (left side of the button) repeatedly to select another address to change. 

Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after 
another. Only the fan and louvers of the selected indoor unit are activated.

Repeat steps 

4

 to 

6

 to change the indoor unit addresses so as to make each of them unique.

7

Push the 

 button.

(All the segments on the LCD display light up.)

8

Push the 

 button to finish the procedure.

Resetting the address
(Resetting to the factory default (address undecided))

Method 1

Clearing each address separately using a wired remote controller.
Set the system address, indoor unit address and group address to “0099” using a wired remote controller.
(For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous 
pages.)

Method 2

Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.

1

Turn off the refrigerant line to reset to the factory default and set the outdoor unit of the line as below.

1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals. 

(Leave them as they are if they have already been disconnected.)

2) Turn on dip switch 2 of SW30 on the interface P.C. board of the outdoor unit if the switch is OFF.

(Leave it as it is if it has already been set to ON.)

UNIT  LOUVER

U1 U2

A B

U1 U2

A B

U1 U2

A B

U1 U2

A B

U1

U3

U2

U4

U1 U2

A B

U4

U3

U2

U1

CN02

CN10

U4

U3

U2

U1

CN02

CN10

U4

U3

U2

U1

CN02

CN10

Remote 

controller

Central controller

Remote 

controller

Remote 

controller

Remote 

controller

Indoor units to have their addresses initialized

Outdoor unit

[U1, U2] and 
[U3, U4] connected

[U1, U2] and 
[U3, U4] connected

[U1, U2] and [U3, U4] 
not connected

Outdoor unit

Outdoor unit

EN-49

EN-50

2FAN_IM_DB04905901-00.book  Page 25  Friday, October 24, 2014  3:19 PM

Содержание MCY-MAP0401TP Series

Страница 1: ...h AIR CONDITIONER MULTI TYPE Installation Manual For commercial use Outdoor Unit Model name MCY MAP0401TP Series MCY MAP0501TP Series MCY MAP0601TP Series 2FAN_IM_DB04905901 00 book Page 1 Friday October 24 2014 3 19 PM 1121701001 ...

Страница 2: ...f if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Do not climb onto or place objects on top of the outdoor unit You may fall or the objects may fall off of the outdoor unit and result in injury When working at height put a sign in place so that no one will approach the work location before proceeding with the work Par...

Страница 3: ...lt in fire When carrying out electric connection use the wire specified in the Installation Manual and connect and fix the wires securely to prevent them applying external force to the terminals Improper connection or fixing may result in fire Test run Before operating the air conditioner after having completed the work check that the electrical parts box cover of the indoor unit and service panel...

Страница 4: ... enter Required tools and cautions on handling It is necessary to prepare the tools and parts for installation as described below The tools and parts which will be newly prepared in the following items should be restricted to exclusive use Explanation of symbols Newly prepared It is necessary to use it exclusively with R410A separately from those for R22 or R407C Former tool is available Used tool...

Страница 5: ...oor unit Insufficient durability may cause the outdoor unit to fall which may result in injury This outdoor unit has a weight of about 74 kg or more Pay special attention when installing the unit onto a wall surface CAUTION Do not install the outdoor unit in a location that is subject to combustible gas leaks Accumulation of combustible gas around the outdoor unit may cause a fire Install the outd...

Страница 6: ...ll the unit so that its discharge port faces the wall of the building Keep a distance 500 mm or more between the unit and wall surface 2 Leave a clearance of at least 250 mm between the right side panel and wall or other surface of the building for installation and servicing purposes 250 mm 3 Leave a clearance of at least 200 mm between the rear panel and wall or other surface of the building in o...

Страница 7: ... and left of the unit The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit Standard installation 1 Single unit installation 2 Serial installation of two or more units Serial installation in front and rear Open above and to the right and left of the unit The height of an obstacle in both the front and rear of the unit should be lower t...

Страница 8: ...utdoor unit connecting pipes can be connected in any of 4 directions Use a screwdriver to punch out the knockout part of the front panel side panel or base Wear heavy work gloves to protect yourself from injury while doing this work After punching out the knockout hole in a manner which ensures that the pipes and wires will not be damaged in any way remove the burrs from around the hole Optional i...

Страница 9: ...1 0 to 1 5 16 6 26 49 to 61 4 9 to 6 1 15 88 1 0 0 to 0 5 1 0 to 1 5 19 7 29 63 to 77 6 6 to 7 7 90 Obliquity Roughness Warp A B REQUIREMENT For a brazing work of the refrigerant pipes be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes otherwise clogging of the refrigerating cycle due to oxidized scale may occur Use clean and new pipes for the refrigerant pipes an...

Страница 10: ...oor unit capacity type Capacity code No of connectable indoor units Total capacity code of connectable indoor units Equivalent to HP Min HP Max HP 040 type 4 2 to 6 3 2 5 2 050 type 5 2 to 6 4 0 6 5 Selection of refrigerant piping No Piping parts Name Selection of pipe size Remarks 1 Outdoor unit 1st branching section Main pipe Size of main pipe Same as connecting pipe size of the outdoor unit 2 B...

Страница 11: ...exceeds the capacity code of the outdoor unit apply the capacity code of the outdoor unit See Table 1 and 2 Outdoor unit capacity type Gas pipe Liquid pipe 0401 type 15 88 9 52 0501 type 15 88 9 52 Total capacity codes of indoor units at down stream side Gas pipe Liquid pipe Equivalent to HP Equivalent to capacity Below 2 4 Below 6 4 12 70 9 52 2 4 or more Below 6 4 15 88 9 52 0601 type 19 05 9 52...

Страница 12: ... outdoor unit 15 m Height between indoor units H2 10 m Outdoor unit 2FAN_IM_DB04905901 00 book Page 11 Friday October 24 2014 3 19 PM L2 L1 d L3 e f Y shaped branching joint Main pipe 1st branching pipe section Branching Branching header Indoor unit pipe Branching Heigh ce betweenindoorand outdoor units H1 Height erence units H2 betweenindoor Equivalent length corresponded to farthest piping after...

Страница 13: ...units to one PMV Kit Arrange one indoor unit and one PMV Kit set to 1 by 1 NO GOOD OK PMV Kit PMV Kit Indoor unit Indoor unit EN 23 EN 24 2FAN_IM_DB04905901 00 book Page 12 Friday October 24 2014 3 19 PM l f a b c H2 H2 H2 L3 A 1 L1 L2 k g h i Height difference between indoor and outdoor units H1 Main pipe section 1st branching Branching pipe header Branching Indoor unit Y shaped branching joint B...

Страница 14: ...anifold Outdoor unit Service port NOTE However if the environmental temperature changes from the moment of applying pressure to 24 hours after that the pressure will change by about 0 01 MPa 0 1 kg cm2 G per 1 C Consider the pressure change when checking the test result REQUIREMENT When pressure decrease is detected in steps 1 3 check the leakage at the connecting points Check the leakage using a ...

Страница 15: ...t Low pressure guage High pressure guage Ball valve fully closed Gas side Flare connection Flare connection Packed valve fully closed Liquid side Service port Vacuum pump Gauge manifold Outdoor unit Service port Adding refrigerant After finishing vacuuming exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant Calculation of additional refrigerant charge ...

Страница 16: ...L5 Ø6 35 3 m L6 Ø6 35 4 m L7 Ø6 35 5 m A MMU AP0154H B MMU AP0094H C MMU AP0074MH D MMD AP0074SPH L1 L2 L3 L4 L5 L6 L7 D C B A Full opening of the valve Open the valves of the outdoor unit fully Liquid side Using a 4mm hexagonal wrench fully open the valve rods Gas side Using a 5mm hexagonal wrench fully open the valve rods Heat insulation for pipe Apply heat insulation of pipe separately at the l...

Страница 17: ...rd model MCA Maximum Circuit Amps MOCP Maximum Overcurrent Protection Amps Model Power Supply Nominal Voltage Phase and frequency MCA A MOCP A MCY MAP0401 220 240 V 50 Hz 27 0 32 0 MCY MAP0501 28 0 32 0 Circuit breaker Earth leakage breaker Main switch Fuse Specifications for communication wiring Design of communication wiring Summary of communication wiring Communication wiring and central contro...

Страница 18: ...3 U4 U1 U2 U1 U3 U2 U4 U1 U2 A B U3 U4 U1 U2 U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 A B U3 U4 U1 U2 U5 U6 U1 U2 A B U1 U2 A B U1 U2 A B U3 U4 U1 U2 U5 U6 L1 L5 L6 L6 L7 L7 L4 3 L 2 L Central controller This system Other system Table 1 Header unit Follower unit Table 1 Table 2 Table 3 Outdoor unit Indoor unit Remote controller Remote controller Remote controller Group control through a remot...

Страница 19: ...Also apply insulating sleeves to the crimping parts Use a driver of appropriate size to fix the terminal screws Design 60245 IEC66 Screw size and tightening torque Wire size 4 0 mm2 Screw size Tightening torque N m Power supply terminal M6 2 5 3 0 Earth screw M6 2 5 3 0 EN 35 EN 36 2FAN_IM_DB04905901 00 book Page 18 Friday October 24 2014 3 19 PM Terminal block Earth screw Power supply Power suppl...

Страница 20: ...g on the power Running the unit is not required for address setting The addresses can be set manually Automatic addressing setting addresses using SW15 on the interface P C board on the outdoor unit Manual addressing setting addresses on the wired remote controller When setting an address manually the wired remote controller must temporarily be paired with an indoor unit one to one when the system...

Страница 21: ...P C board on the outdoor unit of each system Factory default Address 1 NOTE Be sure to set a unique address on each system Do not use a same address as another system refrigerant line or a custom side Example Controlling 2 or more refrigerant lines as a group System wiring diagram Auto 1 Auto 2 Auto 3 U 1 U 1 flash U 1 U 1 light 3 2 4 D600 D601 D602 D603 D604 SW04 SW05 SW15 SW01 SW02 SW03 Outdoor ...

Страница 22: ...ted to the same central control except the unit that has the lowest address For unifying the termination of the wiring for the central control of indoor and outdoor units U1 U2 U3 U4 CN02 CN10 U1 U2 U3 U4 TO INDOOR UNIT TO CENTRAL CONTROLLER U1 U2 and U3 U4 not connected Communication terminal board U 1 L08 U 1 flash Auto 1 Auto 2 Auto 3 U 1 U 1 flash U 1 U 1 light 9 Connect the relay connectors C...

Страница 23: ...e controller Group Individual Indoor units automatic setting Outdoor unit U1 U2 and U3 U4 connected Outdoor unit U1 U2 and U3 U4 connected Outdoor unit U1 U2 and U3 U4 connected Manual address setting with the remote controller Procedure when setting indoor units addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started manual setting using t...

Страница 24: ...west address For unifying the termination of the wiring for the central control of indoor and outdoor units Connect the relay connectors CN10 between the U1 U2 and U3 U4 terminals on the interface P C board to CN02 in all the outdoor units to which the central control is connected After finishing all the settings above set the address of the central control devices For the setting of the central c...

Страница 25: ...ne are indicated one after another Only the fan and louvers of the indicated indoor unit are activated UNIT LOUVER 5 6 1 3 4 2 ON OFF TEMP TIME SET CL FILTER RESET TEST TIMER SET CODENo UNIT No SETTING DATA SET R C No UNIT LOUVER SWING FIX UNIT LOUVER To select another system address 5 Push the button to return to step 2 After returning to step 2 select another system address and check the indoor ...

Страница 26: ...n SET DATA 6 Push the button left side of the button repeatedly to select another address to change Each time you push the button the indoor unit numbers in a refrigerant line are indicated one after another Only the fan and louvers of the selected indoor unit are activated Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique 7 Push the button All the segments ...

Страница 27: ...trol address U 1 A d buS A d nEt A d c L U 1 L08 A d n G 8 Test Run Before test run Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN Before turning on the power confirm that the resistance between the terminal block of power supply and the earth is more than 1 M τ using a 500 V megohmmeter Do not run the unit if it is less than 1 M τ CAUTION Turn on the power and turn on ...

Страница 28: ... units connected are available Individual test run Starting operation 1 Set the running mode to COOL or HEAT on the remote controller of the indoor unit to be tested The unit will run in the current mode unless you set the mode otherwise 2 Set the rotary switches on the interface P C board of the outdoor unit SW01 to 16 SW02 and SW03 to the address of the indoor unit to be tested 3 Push and hold S...

Страница 29: ...es after turning the power on or stopping running 7 segment display A U1 B 7 segment display A C H B 7 segment display A C H B C H Stop operation 1 Set the rotary switches on the interface P C board of the outdoor unit back SW01 to 1 SW02 to 1 and SW03 to 1 7 segment display A U1 B D600 D601 D602 D603 D604 SW04 SW05 SW15 SW01 SW02 SW03 Interface P C board Push switch 7 segment display A Push switc...

Страница 30: ... F24 Pd sensor error F31 Outdoor EEPROM error H01 Compressor breakdown A B D600 D601 D602 D603 D604 H02 Compressor trouble Lock H03 Current detective circuit system error H06 Low pressure proctive operation L04 Outdoor system address duplicated L06 Number of indoor units with priority Duplication of indoor units with priority L08 Indoor group Address unset L10 Outdoor capacity unset L29 IPDU quant...

Страница 31: ...s 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg Total amount of refrigerant kg Min volu...

Страница 32: ......

Отзывы: