Allowable length / height difference of refrigerant piping for quiet places (with PMV Kit)
*1 Furthest indoor unit from 1st branch to be named “A”.
Allowable
value
Pipes
Piping Length
Total extension of pipe (Liquid pipe, real length)
80
m
L1 + L2 + L3 + a + b + c + d + e + f + g + h
+ i + j
+ k +
l
Furthest piping length L
(*1)
Real length
40
m
L1 + L3 +
f
+
l
Equivalent length
50
m
Max. equivalent length of main pipe
2
5
m
L1
Max. real length of furthest piping from 1st
branching Li (*1)
15
m
L3 +
f
+
l
Max. real length of indoor unit connecting pipe
10 m
a +
g
,
b +
h
,
c +
i
,
d +
j
, e +
k, f +
l
Real length between PMV Kit and indoor unit
2 m or more
Below 10 m
g, h, i, j
, k,
l
Height
Difference
Height between indoor
and outdoor units H1
Upper outdoor unit
15 m
Lower outdoor unit
15 m
Height between indoor units (PMV Kit) H2
10 m
Outdoor unit
NOTE
Do not connect two or more indoor units to one PMV Kit. Arrange one indoor unit and one PMV Kit set to 1 by 1.
NO GOOD
OK
PMV Kit
PMV Kit
Indoor unit
Indoor unit
EN-23
EN-24
2FAN_IM_DB04905901-00.book Page 12 Friday, October 24, 2014 3:19 PM
l
f
a
b
c
H2
H2
H2
L3
A
*1
L1
L2
k
g
h
i
Height
difference
between
indoor and
outdoor
units H1
Main
pipe
section
1st branching
Branching
pipe
header
Branching
Indoor unit
Y-shaped
branching joint
Branching pipe
Equivalent length corresponded to farthest piping after 1st branching Li
Equivalent length corresponded to farthest piping L
Height difference
between indoor unit
*
and PMV Kit
H2
*
Between highest
units.
unit and lower
PMV Kit
Example)
d
e
j
Outdoor unit
L
Main pipe
Indoor unit
Hight difference
between indoor and
outdoor unit H
In case of 1 indoor units connecting.
Total extension of pipe
length
Hight difference between indoor and
outdoor unit
Upper outdoor unit
Allowable
7.5 m -
4
0 m
Lower outdoor unit
Pipes
15 m
15 m
L
+l
H
In case of 2 to 6 indoor units connecting.
PMV kit
l
Real length
between PMV kit and indoor unit
2
m -
1
0 m
l