128
Points to Note When Servicing Compressor
(1) When checking the outputs of inverters, remove the wiring from the compressors.
How to Check Inverter Output
(1) Turn off the power supply.
(2) Remove compressor leads from the IPDU P.C. board (A3-IPDU). (Be sure to remove all the leads.)
(3) Turn on the power supply and start cooling or heating operation.
Be careful not to make simultaneous contact with two or more quick connect terminal for compressor leads or a
quick connect terminal and some other object (e.g. the unit cabinet).
(4) Check the output voltage inverter-side (CN201, 202, 203).
If the result is unsatisfactory according to the judgment criteria given in the table below, replace the IPDU P.C.
board.
* When connecting the compressor leads back to the compressor terminals after checking the output, check the
quick connect terminals thoroughly to ensure that they are not crooked. If there is any loose connector, tighten
it with a pair of pliers, etc. before connecting the lead.
How to Check Resistance of Compressor Winding
(1) Turn off the power supply.
(2) Remove compressor leads from the compressors.
(3) With compressor, check the phase-to-phase winding resistances and winding-to-outdoor cabinet resistance
using a multimeter.
Earth fault?
It is normal if the winding-to-outdoor cabinet resistance is 10 M or more.
Inter-winding short circuit?
It is normal if the phase-to-phase resistances are in the 0.6-1.0 range. (Use a digital multimeter.)
How to Check Outdoor Fan Motor
(1) Turn off the power supply.
(2) Remove fan motor leads from the IPDU P.C. board for the outdoor fan (CN750 (Lower side FM), CN700 (Upper
side FM)).
(3) Rotate the fan by hand. If the fan does not turn, the fan motor is faulty (locked up). Replace the fan motor.
If the fan turns, measure the phase-to-phase winding resistances using a multimeter. It is normal if the
measurements are in the 15.6-19.0 range. (Use a digital multimeter.)
No.
Measured leads
Criterion
1
Red-White
200-280V
2
White-Black
200-280V
3
Black-Red
200-280V
118
A10-1510.indb 118
A10-1510.indb 118
2016/04/08 17:21:10