153
Step Component
Procedure
Remarks
2
Discharge
cabinet
1. Detachment
1) Remove the front panels and upper panel.
[Step.1]
2) Remove the screws of the discharge cabinet
(upper), top of the heat exchanger plate.
(M4×10, 1 ) (Fig. 2-1)
Heat exchanger (upper)
screw (1 position)
(Fig. 2-1)
3) Remove the screws of the discharge cabinet
(upper) and discharge cabinet (lower).
(M4×10, 2 ) (Fig. 2-4)
4) Remove the screws of the discharge cabinet
(upper) and
fi
n guard (upper).
(M4×10, 3 ) (Fig. 2-3)
5) Remove the screws of the discharge cabinet
(upper) and inverter assembly.
(M4×10, 4 ) (Fig. 2-4)
* Remove the screws of the discharge cabinet
(lower) and partition plate.
(M4×10, 3 ) (Fig. 2-5)
6) Remove the screws of the discharge cabinet
(upper) and motor base.
(M4×10, 2 ) (Fig. 2-6)
Motor base
screws (2 positions)
(Fig. 2-6)
7) As in steps 2) to 6), remove the discharge
cabinets (lower).
2. Attachment
1) Mount by reversing the detachment procedure,
attaching the lower and upper discharge
cabinets in order.
• Insert the hooking tabs into the holes in the
motor base and fix each discharge cabinet in
place with screws. (Fig. 2-7)
Hooking tabs
(Fig. 2-7)
Discharge
cabinet (lower)
screws (3 positions)
bottom plate
screws (2 positions)
Fin guard screws
(3 positions)
Inverter assembly
Discharge
cabinet (lower)
screws (2 positions)
screws (4 positions)
Discharge
cabinet (upper)
Discharge
cabinet (upper)
Discharge
cabinet (lower)
(Fig. 2-2)
(Fig. 2-3)
(Fig. 2-4)
(Fig. 2-5)
A10-1510.indb 153
A10-1510.indb 153
2016/04/08 17:21:23
2016/04/08 17:21:23