117
Other (indications not involving check code)
F04
Discharge temperature sensor (TD) trouble
Outdoor unit temperature sensor
troubles
F06
Heat exchanger temperature sensor (TE) trouble
F07
Liquid temperature sensor (TL) trouble
F08
Outside air temperature sensor (TO) trouble
F12
Suction temperature sensor (TS) trouble
F13
Heat sink sensor (TH) trouble
F15
Wiring trouble in heat exchanger sensor (TE) and liquid temperature sensor (TL)
Outdoor unit temperature sensor wiring / installation trouble
F16
Wiring trouble in outdoor high pressure sensor (PD) and low pressure sensor (PS)
Outdoor pressure sensor wiring trouble
F23
Low pressure sensor (PS) trouble
Outdoor unit pressure sensor troubles
F24
High pressure sensor (PD) trouble
F29
Trouble
in indoor EEPROM
H01
Compressor breakdown
Outdoor unit compressor-related troubles
H02
Compressor lockup
H03
Current detection circuit trouble
H04
Comp. case thermostat operation
H06
Abnormal drop in low-pressure sensor (PS) reading
Protective shutdown of outdoor unit
L03
Duplicated indoor group outdoor unit
L05
Duplicated priority indoor unit (as displayed on priority indoor unit)
L06
Duplicated priority indoor unit (as displayed on indoor unit other than priority indoor unit)
L07
Connection of group control cable to stand-alone indoor unit
L08
Indoor group address not set
L09
Indoor capacity not set
L04
Duplicated outdoor refrigerant line address
L10
Outdoor capacity not set
L29
Trouble in number of IPDUs
L30
Indoor external interlock trouble
F31
Outdoor EEPROM trouble
check code
f
o
e
s
u
a
C
e
d
o
c
k
c
e
h
C
k
c
o
l
b
t
h
g
i
L
–
Test run in progress
–
Setting incompatibility
(automatic cooling / heating setting for model incapable of it and heating setting for cooling-only
model)
check code
f
o
e
s
u
a
C
e
d
o
c
k
c
e
h
C
k
c
o
l
b
t
h
g
i
L
Operation
Timer
Ready
Alternate blinking
Operation
Timer
Ready
Synchronized blinking
Operation
Timer
Ready
Blinking
Operation
Timer
Ready
Synchronized blinking
Operation
Timer
Ready
Synchronized blinking
Operation
Timer
Ready
Synchronized blinking
Operation
Timer
Ready
Synchronized blinking
Operation Timer
Ready
Alternate blinking
106
A10-1510.indb 106
A10-1510.indb 106
2016/04/08 17:21:07
2016/04/08 17:21:07