99
8-7-3. Check code clearing function
(1)Clearing from the main remote controller
Check code clearing in outdoor unit
Check code of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which
the indoor units operated by the remote controller is connected. (Check code of the indoor unit is not cleared.)
For clearing check codes, the service monitor function of the remote controller is used.
<Method>
1
Change the mode to service monitor mode by pushing
+
buttons simultaneously for 4
seconds or more.
2
Using
buttons, set CODE No. to “FF”.
3
The display in Section A in the following figure is counted with interval of 5 seconds as
“0005” --> “0004” --> “0003” --> “0002” --> “0001” --> “0000”.
When the count arrives “0000”, the check code is cleared.
*However, counting from “0005” is repeated on the display.
4
When
button is pushed, the status returns to the normal status.
Check code clearing in indoor unit
Check code in the indoor unit is cleared by
button on the remote controller.
(Only check code of the indoor unit connected with operating remote controller is cleared.)