– 6 –

EN

Obstacle also at the upper side

Obstacles at both front and rear 

sides

Open the upper side and both right and left sides.
The height of obstacle at both front and rear side should be 
lower than the height of the outdoor unit.

Standard installation

1. Single unit installation

2. Serial installation of two or more units

Serial installation at front and rear 

sides

Open the upper side and both right and left sides.
The height of obstacle at both front and rear sides should be 
lower than the height of the outdoor unit.

Standard installation

„

Installation of outdoor unit

• Before installation, check strength and horizontally of the 

base so that abnormal sound does not generate.

• According to the following base diagram, fix the base firmly 

with the anchor bolts. 
(Anchor bolt, nut: M10 x 4 pairs)

Set the out margin of the anchor bolt to 15 mm or less.

• In case of draining through the drain hose, attach the 

following drain nipple and the waterproof rubber cap, and 
use the drain hose (Inner diam.: 16 mm) sold on the 
market. And also seal the screws securely with silicone 
material, etc. so that water does not drop down. Some 
conditions may cause dewing or dripping of water.

• When there is a possibility of freezing of drain at the cold 

district or a snowfall area, be careful for drainage ability of 
drain. The drainage ability increases when a knockout hole 
on the base plate is opened. (Open the knockout hole to 
outside using a screwdriver, etc.)

1

000

 or

 mor

e

1000

 or more

100

0

 or

 m

o

re

15

0

 or

 mo

re

1000

 or

 mor

e

200

 or

 mor

e

300

 or more

300

 or more

1000

 or more

300

 or more

1500

 or more

2000

 or more

200

 or more

600

0

5

1

0

5

1

430

365

40

400

Knockout hole

Drain hole

Drain nipple mounting hole

15 or less

Drain nipple

Waterproof rubber cap

Drain nipple

Waterproof rubber cap

Knockout hole

Open

„

Refrigerant piping connection

CAUTION

Take notice these important
4 points below for piping work

1. Keep dust and moisture away from inside the 

connecting pipes.

2. Tightly connect the connection between pipes and 

the unit.

3. Evacuate the air in the connecting pipes using 

VACUUM PUMP.

4. Check gas leak at connected points.

„

For reference

If a heating operation would be continuously performed for a 
long time under the condition that the outdoor temperature is 
0 °C or lower, draining of defrosted water may be difficult due 
to freezing of the bottom plate, resulting in a trouble of the 
cabinet or fan.
It is recommended to procure an anti-freeze heater locally for 
a safety installation of the air conditioner.
For details, contact the dealer.

„

Knockout of pipe cover

Knockout procedure

• The indoor / outdoor connecting pipes can be connected to 

4 directions.
Take off the knockout part of the pipe cover in which pipes 
or wires pass through the base plate.

• As shown in the figure, do not remove the pipe cover from 

the cabinet so that the knockout hole can be easily 
punched. To knock out, it is easily taken off by hands by 
punching a position at the lower side of 3 connected parts 
with screwdriver along the guide line.

• After marking the knockout hole, remove the burr and 

mount the attached protective bush and guard material for 
pass-through part in order to protect pipes and wires.

After connecting the pipes, be sure to mount the pipe cover. 
The pipe cover is easily mounted by cutting off the slit at the 
lower part of the pipe cover.

How to remove the front panel

1. Remove screws of the front panel.
2. Pull the front panel downward.

Removing the front panel, the electric parts appear at the 
front side.
• The metal pipes are attachable to the piping holes. If the 

size of the used power pipe does not match with the hole, 
adjust the hole size to match with pipe size.

• Be sure to fix the power cable and indoor / outdoor 

connecting cable with bundling band sold on the market so 
that they do not make contact with the compressor and 
discharge pipe. 
(Temperature of the compressor and discharge pipe 
becomes high.)
In order to avoid the force applied to on the connecting 
section, be sure to fix the cables to the cord clamps 
provided on the pipe valve fixing plate and the electrical 
control box.

Rear direction

Side direction

Pipe cover

Down direction

Front direction

Electrical control box

Terminal 
plate

Cord clamp

Front panel

11-EN

12-EN

Содержание MAP0601HT2DZG

Страница 1: ...01HT MCY MAP0601HT MCY MAP0401HTZ MCY MAP0501HTZ MCY MAP0601HTZ MCY MAP0401HTZG MCY MAP0501HTZG MCY MAP0601HTZG For commercial use Installation Manual English MCY MAP0401HT2D MCY MAP0501HT2D MCY MAP0601HT2D MCY MAP0401HT2DZ MCY MAP0501HT2DZ MCY MAP0601HT2DZ MCY MAP0401HT2DZG MCY MAP0501HT2DZG MCY MAP0601HT2DZG ...

Страница 2: ...matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation re...

Страница 3: ... undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the outdoor unit You may injure yourself if you do so If the fin must be touched for some reason first put on protective gloves and safety work clothing and then proceed Do not climb onto or place objects on top of the outdoor unit You may fall or the objects ...

Страница 4: ...are closed and set the circuit breaker to the ON position You may receive an electric shock if the power is turned on without first conducting these checks When you have noticed that some kind of trouble such as when an error display has appeared there is a smell of burning abnormal sounds are heard the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner d...

Страница 5: ...rigerant Accordingly exclusive tools are required for the new refrigerant R410A as shown below For connecting pipes use new and clean piping materials so that water or dust does not enter Required tools and cautions on handling It is necessary to prepare the tools and parts for installation as described below The tools and parts which will be newly prepared in the following items should be restric...

Страница 6: ...s feet There must be sufficient space for carrying in the unit A place where the drain water does not make any problem CAUTION 1 Install the outdoor unit at a place where discharge air is not blocked 2 When an outdoor unit is installed in a place that is always exposed to a strong wind like a coast or on a high story of a building secure a normal fan operation by using a duct or a wind shield 3 Wh...

Страница 7: ...t 3 Evacuate the air in the connecting pipes using VACUUM PUMP 4 Check gas leak at connected points For reference If a heating operation would be continuously performed for a long time under the condition that the outdoor temperature is 0 C or lower draining of defrosted water may be difficult due to freezing of the bottom plate resulting in a trouble of the cabinet or fan It is recommended to pro...

Страница 8: ...5 1 5 to 2 0 1 0 to 1 5 15 9 2 0 to 2 5 1 5 to 2 0 A 0 0 4 B Tightening of connecting part Unit N m Align the centers of the connecting pipes and tighten the flare nut strong as far as possible with your fingers Then fix the nut with a spanner and tighten it with torque wrench as shown in the figure As shown in the figure be sure to use a double spanner to loosen or tighten the flare nut of the va...

Страница 9: ...ecided at each capacity rank The maximum No of connectable indoor unit and the total value of capacity codes of the indoor units are also decided Connected section External size Internal size Standard outer dia of connected copper pipe Connected section Min thickness of coupling External size Internal size Min depth of insertion Oval value Standard outer dia Allowable difference C F K G 6 35 6 35 ...

Страница 10: ...lection of refrigerant piping for quiet place with PMV Kit No Piping parts Name Selection of pipe size Outdoor unit È 1st branching section Main pipe Size of main pipe Branching section È Branching section Branching pipe Pipe size between branching sections If the total capacity code value of indoor units exceeds that of the outdoor units apply the capacity code of outdoor units Branching section ...

Страница 11: ...from 1st branch to be named A NOTE Do not connect two or more indoor units to one PMV Kit Arrange one indoor unit and one PMV Kit set to 1 by 1 Allowable value Pipes Piping Length Total extension of pipe Liquid pipe real length 150 m L1 L2 L3 L4 a b c d e f g h I j k l m n Furthest piping length L 1 Real length 65 m L1 L3 L4 g n Equivalent length 80 m Max equivalent length of main pipe 50 m L1 Equ...

Страница 12: ...r the air purge at installation time Discharge of air in connecting pipes use Vacuum pump method from viewpoint of the protection of the earths environment For protection of the earth environment do not discharge the refrigerant gas in the air Using a vacuum pump eliminate the remaining air nitrogen gas etc in the unit If gas remains performance and reliability of the unit may be reduced After the...

Страница 13: ...on The refrigerant amount at shipment is indicated on the unit name plate Additional refrigerant charge R kg amount at site Real length of liquid pipe Additional refrigerant charge amount per liquid pipe 1m Table 1 Compensation by outdoor HP Table 2 Table 1 Table 2 L1 Ø9 5 10 m L2 Ø9 5 10 m L3 Ø9 5 5 m a Ø9 5 3 m Ø6 4 3 m c Ø6 4 4 m d Ø6 4 5 m NOTE If the additional refrigerant amount indicates a ...

Страница 14: ...upply capacity or inappropriate installation may cause a fire When connecting the installation wiring be sure that all fixing terminal are securely fixed Ensure earthling practice is correctly performed Grounding is necessary if earthling practice is incomplete an electric shock maybe caused CAUTION The installation fuse must be used for the power supply line of this outdoor unit Incorrect incompl...

Страница 15: ...arth leakage breaker Outdoor unit power supply N L 10 L N 10 50 90 Power cable Earth wire Power cable Terminal block Stripping length power cable Protective bush Accessory Cord clamp For Indoor unit power supply The outdoor unit has a separate power supply NOTE Power supply cord specification Cable 3 core 2 5 mm inconformity with Design 60245 IEC57 The connecting length indicated in the table repr...

Страница 16: ... 2 No 3 No 4 No 7 No 8 Connect each wire for controlling as shown below Wire specification quantity size of crossover wiring and remote controller wiring 1 The crossover wiring and central control wiring use 2 core non polarity transmission wires Use 2 core shield wires to prevent noise trouble In this case close connect the end of shield wires and perform the functional grounding for the end of t...

Страница 17: ...rth Earth Earth Earth Earth Option Outdoor power supply MCY MAP HT 1N 50 Hz 220 V 240 V MCY MAP HT2D 1N 60 Hz 220 V Central remote controller power supply 1N 50 Hz 220 V 240 V 1N 60 Hz 220 V Outdoor unit Indoor unit Remote controller Central remote controller Option Over current breaker Fuse switch Earth leakage breaker Main switch Pull box PMV Kit Option 7 Installation of outdoor unit When using ...

Страница 18: ...erformed by power ON only 5 To set up an address the air conditioner does not need to be in operation 6 Manual address setup is also available besides automatic setup Automatic address Setup from SW15 on the interface P C board of the outdoor unit Manual address Setup from the wired remote controller It is temporarily necessary to set up the indoor unit as a 1 1 using a wired remote controller Aut...

Страница 19: ...12 13 14 Line address SW13 SW14 1 2 3 4 1 2 3 4 15 16 17 18 19 20 21 22 23 24 25 26 27 28 U2 U1 U3 U4 Relay connector For control wiring between indoor and outdoor For wiring of central control system 2 U 1 L08 U 1 flash Auto 1 Auto 2 Auto 3 U 1 U 1 flash U 1 U 1 light 8 When address setup has finished in all the systems turn off SW30 2 on the interface P C boards of the lines connected to the ide...

Страница 20: ...29 and 30 The address 29 and 30 cannot be set up in the outdoor unit Therefore if they are incorrectly set up a check code E04 Indoor outdoor communication circuit error will be displayed 2 When an address has been manually setup from the wired remote controller and you wish to set up a central control over the refrigeration system and setup the outdoor unit for each system using the following ste...

Страница 21: ...operates To select another system address 5 Push button to return to procedure 2 The indoor address of another line can be successively confirmed 6 Push button to finish the procedure 3 1 2 1 TEMP ON OFF SET TIME TEST FILTER RESET CL SAVE SWING FIX VENT UNIT LOUVER CODE No UNIT No R C No E D O M T E S R E M I T FAN SETDATA SETTING Operation procedure 1 2 3 End End VENT TEST TEST TEST 5 6 1 3 2 4 T...

Страница 22: ...ed from a wired remote controller 0099 is set up to line address indoor address and group address data from the wired remote controller For the setup procedure refer to the above mentioned address setup from the wired remote controller Method 2 Clear the indoor addresses in the same refrigerant system from the outdoor unit 1 Turn off the power of the refrigerant system to be returned to the status...

Страница 23: ...utdoor unit This air conditioner has a function which executes a test run by operation of the switches on the interface P C board of the outdoor unit This function is classified into Individual test run which performs a test run individually in each indoor unit and Collective test run which performs a test run for all the connected indoor units Individual test run Collective test run Procedure Ope...

Страница 24: ...quantity information IPDU communication error F04 TD1 sensor error F06 TE1 sensor error F07 TL sensor error F08 TO sensor error F12 01 TS1 sensor error TS1 sensor error F13 01 Compressor 1 TH sensor error F15 Outdoor temp sensor miswiring TE TL F16 Outdoor pressure sensor miswiring Pd Ps F23 Ps sensor error F24 Pd sensor error F31 Outdoor EEPROM error D600 A B D601 D602 D603 D604 H01 01 Compressor...

Страница 25: ... 24 MEMO ...

Страница 26: ... 25 MEMO ...

Страница 27: ... 26 MEMO ...

Страница 28: ... air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards...

Отзывы: