– 23 –
10
Troubleshooting
In addition to the check code on the remote controller of the indoor unit, a trouble of the outdoor unit can be
diagnosed by 7-segment display of the control P.C. board of the outdoor unit. Make good use of this function for
various checks. After check, return each bit of Dip switch to OFF position.
▼
Segment display and check code
* However, when there is an auxiliary code, the check code (for 3 seconds) and the auxiliary code (for 1 second)
are alternately displayed.
Check Code (Outdoor 7-segment display [B])
Displayed when SW01: 1, SW02: 1, SW03: 1
Rotary switch setup value
Displayed contents
LED
SW01
SW02
SW03
1
1
1
Check code of outdoor unit
A
Outdoor unit No. (U1 only)
B
Check code display*
Check code
Outdoor 7-segment display
Auxiliary code
Check code name
E06
Number of indoor unit which received normally
Decrease of number of indoor units
E07
—
Indoor / Outdoor communication circuit error
E08
Duplicated indoor addresses
Duplication of indoor addresses
E12
01: Communication between indoor and outdoor
02: Communication between outdoor units
Automatic address start error
E15
—
Indoor is nothing during automatic
addressing
E16
00: Capacity over 01~: No. of connected units
Capacity over / Number of connected
indoor units
E19
00: Header is nothing
02: Two or more header units
Number of header outdoor units error
E20
01: Other system outdoor connected
02: Other system indoor connected
Other refrigerant system connected during
automatic addressing
E31
IPDU quantity information
IPDU communication error
F04
—
TD1 sensor error
F06
—
TE1 sensor error
F07
—
TL sensor error
F08
—
TO sensor error
F12
01: TS1 sensor error
TS1 sensor error
F13
01: Compressor 1
TH sensor error
F15
—
Outdoor temp. sensor miswiring (TE, TL)
F16
—
Outdoor pressure sensor miswiring (Pd, Ps)
F23
—
Ps sensor error
F24
—
Pd sensor error
F31
—
Outdoor EEPROM error
D600
A
B
D601 D602 D603 D604
H01
01: Compressor 1
Compressor breakdown
H02
01: Compressor 1
Magnet switch error
Over-current relay operation
Compressor trouble (Lock)
H03
01: Compressor 1
Current detective circuit system error
H04
—
Compressor 1 case thermo operation
H06
—
Low-pressure protective operation
L04
—
Outdoor line address duplicated
L06
Number of indoor units with priority
Duplication of indoor units with priority
L08
—
Indoor group / Address unset
L10
—
Outdoor capacity unset
L18
Detected indoor address
Flow selector unit error
L29
IPDU quantity information
IPDU quantity error
L30
Detected indoor address
External interlock of indoor unit
L31
—
Extended I/C error
P03
—
Discharge temp TD1 error
P04
01: Compressor 1
High-pressure SW system operation
P07
01: Compressor 1
Heat sink overheat error
P10
Detected indoor address
Indoor overflow error
P13
—
Outdoor liquid back detection error
P15
01: TS condition
02: TD condition
Gas leak detection
P19
Detected outdoor unit number
4-way valve inverse error
P20
—
High-pressure protective operation
P22
* A : Fan motor circuit error
* d : Fan motor lock
Outdoor fan IPDU error
P26
01: Compressor 1
IGBT short protection error
P29
01: Compressor 1
Compressor position detective circuit
system error
Check code
Outdoor 7-segment display
Auxiliary code
Check code name
45-EN
46-EN